Date |
Text |
2008-08-27 11:25:12 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| PLAN REVIEW ONLY |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. OK |
| 8. OK |
| 9. OK |
| |
| ***********NEW COMMENTS*********** |
| |
| NEW PLUMBING SHEETS SUBMITTED |
| |
| 1B. SHT P-2 SANITARY RISER ISOMETRIC DOES NOT REFLECT |
| THE FLOOR PLAN. STACK WITH DOUBLE LAV'S P-3 SHOWS A |
| TRAP TO THE STORAGE ROOM ON THE FLOOR PLAN THAT IS NOT |
| ON THE RISER DIAGRAM.--THE FLOOR PLAN SHOWS A FLOOR |
| DRAIN IN THE STORAGE AREA THAT CONNECTS UPSTREAM OF THE |
| URINALS IN THE MEN'S ROOM 116 THAT IS NOT SHOWN ON THE |
| RISER DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1 & |
| 704.--FLOOR DRAIN UPSTREAM OF THE URINALS APPEARS |
| TO EXCEED THE MAXIMUM DISTANCE FROM THE VENT PER TABLE |
| 906.1. |
| |
| 2B. SHT P-2 DOMESTIC WATER PIPING ISOMETRIC DOES NOT |
| REFLECT THE FLOOR PLAN NOR DOES IT REFLECT THE PLUMBING |
| FIXTURE SCHEDULE SHOWN ON SHT P-3. RISER SHOWS A |
| FIXTURE P-9 DOWNSTREAM OF FIXTURE P-7 IN THE STORAGE |
| (117) ROOM. THIS IS NOT SHOWN ON THE FLOOR PLAN NOR ON |
| THE FIXTURE SCHEDULE. PLEASE CORRELATE. SECTIONS |
| 106.1.1 & 604. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |