2008-09-04 09:26:39TEMPORARY FAIL:
  
 MISSING ONE SET OF ENERGY CALCULATIONS AND 2 SETS OF
 COOLING LOAD CALCULATIONS. SPOKE TO KEVIN. IF MISSING
 DOCUMENTS ARE PROVIDED PRIOR TO COMPLETION OF ALL
 REVIEWS, THEY WILL BE INCORPORATED INTO THE SUBMITTAL
 AND MECHANICAL REVIEW WILL PASS.
  