Plan Review Notes
Plan Review Notes For Permit 07090553
Permit Number 07090553
Review Stop E
Sequence Number 3
Notes
Date Text
2008-09-04 13:06:12 
  
  
  
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
  
 1) NOTE: PLEASE BE SURE TO SUBMIT TWO COPIES OF ALL
 DOCUMENTS. ONLY ONE SPECIFICATION BOOK WITH
 CALCULATIONS AND MANUFACTURES SPECS WAS LOCATED. IF
 THIS HAD BEEN THE ONLY COMMENT THE SECOND SET COULD
 HAVE BEEN BROUGHT IN.
 FBC 106.1
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO THE ENERGY CALCULATIONS. THE VERSION 3.0 AS
 SUBMITTED IS NOT ADOPTED BY THE FLORIDA BUILDING CODE.
 PLEASE GO TO THE FLORIDA SOLAR ENERGY/ENERGY GAUGE
 WEBSITE AS THERE IS A PATCH/UPDATE TO CORRECT ANY
 PROGRAMS SOLD WHICH SHOW THE 3.0. THIS SHOULD BE
 *VERSION 2.5*. THE STATE AS WELL AS FLORIDA
 SOLAR/ENERGY GAUGE IS AWARE OF THIS ISSUE.
 FBC 13-400.3.A
  
 3) NOTE: PLEASE MAKE SURE ALL LIGHTING AS SHOWN ON
 PLANS AS WELL AS OTHER BUILDING COMPONENTS ARE PLACED
 IN THE INPUT DATA REPORT. THIS INFORMATION FOR ALL
 SYSTEMS AND COMPONENTS IS REQUIRED TO COORDINATE.
 PLEASE SEE THE PREVIOUS REVIEW AS SOME EXAMPLES WERE
 GIVEN YET SOME OF THESE ARE STILL THE SAME. THE
 EXAMPLES ONCE AGAIN IS THE EXTERIOR LIGHTING ON THE IDR
 WHICH IS *BLANK*. THIS IS NOT POSSIBLE WHEN THE PLANS
 CLEARLY SHOW EXTERIOR LIGHTING.
 PLEASE SEE ANOTHER EXAMPLE IS INTERIOR LIGHTING. THERE
 ARE ONLY TWO TYPES OF LIGHTING FIXTURES ON THE IDR YET
 BASED ON THE PLANS SUBMITTED THERE IS A FAR GREATER
 NUMBER OF FIXTURE TYPES.
 ** THESE ARE ONLY TWO EXAMPLES: THERE ARE OTHER ITEMS.
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO A
 REQUIRED GROUNDING ELECTRODE RISER TO BE SHOWN FOR THE
 ATTACHMENT OF ALL TRANSFORMERS.
 THE RESPONSE MENTIONS TO SEE RISER AND NEW NOTES
 HOWEVER THIS ONLY ADDRESSES THE ONE TRANSFORMER ON THE
 LINE SIDE OF SERVICE. THE PREVIOUS COMMENT REFERENCE
 CODES FOR OTHER TRANSFORMER SUCH AS SHOWN ON RISER.
 250.20,250.30,250.58 AND 250.66
 ** PLEASE CALL TO GO OVER IF THERE ARE ANY QUESTIONS.
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS IS ONLY
 THE SECOND REVIEW UNDER PERMIT APPLICATION THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  