Date |
Text |
2008-06-02 08:33:25 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| PLAN REVIEW ONLY |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| |
| 5. PER SECTION 11-4.1.3(10)(B) WHERE MORE THAN ONE |
| DRINKING FOUNTAIN IS PROVIDED, AT LEAST 50% SHALL BE |
| ACCESSIBLE. 3 DRINKING FOUNTAINS ARE SHOWN, 2 SHALL BE |
| ACCESSIBLE. |
| ****RESPONSE NOTED, BUT THE TWO DRINKING FOUNTAINS IN |
| THE CORRIDOR ARE HI/LOW AND AS SUCH ONLY THE LOW |
| DRINKING FOUNTAIN IS ACCESSIBLE. THE HI DRINKING |
| FOUNTAIN MEETS THE CODE REQUIREMENT FOR SECTION |
| 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. THE DRINKING FOUNTAIN |
| IN THE WORKSHOP AREA SHALL BE ACCESSIBLE. THERE IS NO |
| PROVISIONS IN THE CODE FOR EQUIVALENT PROVISIONS AT THE |
| SINK IN THE LUNCH ROOM. PLEASE SHOW 2 OF THE 3 DRINKING |
| FOUNTAINS TO BE ACCESSIBLE. (SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS). |
| |
| 6. OK |
| 7. OK |
| 8. OK |
| 9. OK |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |