2008-06-24 13:13:37*****DENIED*****
  
 ## PREVIOUS COMMENTS (WHICH STILL NEED TO BE
 ADDRESSED):
  
 04. LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS TO
 FIRE PROTECTION EQUIPMENT AND DEVICES. COULD NOT LOCATE
 COMMENT AS INDICATED IN YOUR RESPONSE
  
 07. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING. INDICATE WHICH
 EXTERIOR ELEVATION WOULD BE THE FRONT OR MAIN ENTRANCE
 TO THE BUILDING. AS PER WEST PALM BEACH CODE, ADDRESSES
 SHALL BE POSTED ON THAT PORTION OF THE STRUCTURE
 FRONTING OR FACING UPON THE STREET OR PRINCIPAL
 VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE VISIBLE
 TO APPROACHING VEHICLES.
  
 11. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE
 EQUIPPED WITH KNOX LOCKING CAPS. FOR APPLICATIONS,
 CONTACT WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724. ADD COMMENT TO SHEET FP-1
  
 12. ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE. ADD COMMENT
 TO SHEET C-3 AND/OR SHEET FP-1.
  
 ## NEW COMMENT:
 AA. ON SHEET E-6, THERE IS AN EMERGENCY LIGHT
 ILLUSTRATED ON THE SOUTH WALL OF THE TOOL STORAGE (ROOM
 120) BUT NONE ILLUSTRATED ON SHEETS LS-1 AND A-2;
 PLEASE CORRELATE THE PLAN SHEETS TO REFLECT SAME
 LOCATION AND/OR NUMBER OF DEVICES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722