Date |
Text |
2008-06-13 12:48:49 | ** DENIED ** |
| |
| THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION, |
| SECOND REVIEW TOTAL. PLANS WERE ONLY SUBMITTED FOR |
| *PLAN REVIEW* FIRST TIME. |
| |
| ** PLEASE SEE SOME ITEMS ARE STILL IN NEED OF |
| ADDRESSING FROM PREVIOUS REVIEW. THERE ARE ALSO SOME |
| NEW COMMENTS FOR CHANGES MADE TO PLANS. |
| |
| 1) NOTE: PLEASE BE SURE THE ADDRESS OF THE PROJECT IS |
| CORRECTED ON PLANS. THE APPLIED ADDRESS LOCATION AS |
| GIVEN ON PREVIOUS REVIEW IS 6255 N JOG RD. HOWEVER THE |
| PLANS AND CALCULATIONS NOW HAVE 6527 N JOG RD. IT IS |
| UNCLEAR WHERE THIS NEW NUMERICAL DESIGNATION IS COMING |
| FROM. THE PERMIT APPLICATION SUBMITTED CONTAINS 6255. |
| PLEASE BE SURE TO CORRECT ALL TITLE BLOCKS ON PLANS FOR |
| ALL TRADES WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| REVIEWER(S). |
| ** PLEASE KNOW THAT ANY SHEETS WHICH DO NOT NEED TO BE |
| REPRINTED FOR CORRECTIONS MAY HAVE THE ADDRESS |
| CORRECTED BY HAND IN A NEAT FASHION. IF THERE ARE ANY |
| QUESTIONS ON THIS PLEASE CALL. |
| FAC61G15-23.002, 61G1-16.004, FBC ADMIN SECTIONS |
| 106.3.5.1.2, 106.5 |
| |
| 2) NOTE: PLEASE SEE THE PERMIT APPLICATION SHOWS IN |
| DESCRIPTION THE APPLIED SQ FT AS 11,900 SQ FT AND ALSO |
| AS 11,900,000 SQ FT. THIS SEEMS TO BE DONE IN ERROR. |
| PLEASE KNOW HOWEVER THE ENERGY CALCULATIONS SHOW A SQ |
| FT FOR CONDITIONED AND UN-CONDITIONED SPACE AS ONLY |
| 6120 SQ FT. THE ARCHITECTURAL SHEETS SHOW AS HIGHER SQ |
| FOOTAGE THAN THE CALCULATIONS. |
| FBC 106.1.2 FOR COORDINATION. |
| |
| 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE NOW |
| JUST BEING SUBMITTED FOR THE FIRST REVIEW. THE ENERGY |
| CALCULATIONS SUBMITTED ARE NOT CODE COMPLIANT IN |
| SEVERAL LOCATIONS. COMPONENTS OF THE BUILDING AND |
| MECHANICAL SYSTEM ARE NOT COMMENTED ON BY THIS REVIEWER |
| ALTHOUGH ALL SYSTEMS ON PLANS ARE REQUIRED TO |
| COORDINATE WITH THE SUBMITTED CALCULATIONS AND INPUT |
| DATA REPORT. IN THE REMAINDER OF THIS COMMENT THE INPUT |
| DATA REPORT WILL BE NOTED AS IDR. |
| PLEASE BE SURE ALL LIGHTING ON PLANS IS ACTUALLY PLACED |
| INTO THE IDR. THERE ARE SEVERAL ITEMS WHICH ARE NOT |
| SHOWN. THE FOLLOWING ARE SOME EXAMPLES GIVEN AS A |
| BENEFIT ONLY AND ARE IN NO WAY ALL POSSIBLE ITEMS WHICH |
| DO NOT COMPLY. THIS IS NOT AN EXHAUSTED LIST. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE IDR FOR EXTERIOR LIGHTING. THIS IS BLANK |
| WITH NO LIGHTING AT ALL SHOWN. HOW IS THIS POSSIBLE |
| WHEN THE PLANS CLEARLY SHOW SEVERAL EXTERIOR FIXTURES? |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE IDR FOR INTERIOR LIGHTING. HOW IS IT |
| POSSIBLE THIS SHOWS ONLY THREE TYPES OF FIXTURES WHEN |
| THE PLANS CLEARLY SHOW SEVERAL OTHER TYPES AND |
| WATTAGES? |
| PLEASE SEE THAT ALL LIGHTING ON PLANS AND LIGHTING |
| FIXTURE LEGEND COORDINATE WITH THE IDR. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE SQUARE FOOTAGE AS NOTED ABOVE IN NOTE #2 |
| DOES NOT COORDINATE WITH PLANS PR PERMIT APPLICATION. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE METHOD OF CONTROL CAN NOT BE *MANUAL |
| ON/OFF? WHEN THERE IS CLEARLY AUTOMATED CONTROLS FOR |
| LOCATIONS IN AND OUTSIDE THE BUILDING. |
| |
| ** AS NOTED ABOVE THIS IS A BRIEF LIST FOR BENEFIT ONLY |
| AND IS NOT A LIST OF ALL ITEMS WHICH DO NOT CORRELATE. |
| THERE ARE OTHER ITEMS. |
| PLEASE SEE 13-415.2.ABC.1.1, .1.2, .1.3, 13-415.2 ETC |
| |
| 4) NOTE: PLEASE SEE THE VERSION OF CALCULATIONS |
| SUBMITTED IS REQUIRED TO BE FLA/COM 2.5. PLEASE SEE |
| 13-400.3.A AS THE VERSION SUBMITTED IS NOT YET ADOPTED |
| BY THE FLORIDA BUILDING CODE. THIS HAS BEEN CONFIRMED |
| DIRECTLY WITH THE FLORIDA BUILDING COMMISSION. |
| |
| 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| SHEETS FOR THE FOLLOWING ITEMS AS REQUESTED ON PREVIOUS |
| REVIEW. THE RESPONSE LETTER MENTIONS THESE WERE |
| VERIFIED FOR LISTING AND SUBMITTED HOWEVER THEY COULD |
| NOT BE LOCATED IN ANY DOCUMENTS SUBMITTED. THE RESPONSE |
| MENTIONS THE CONTRACTOR MAY CHANGE DURING THE |
| CONSTRUCTION PROCESS. THIS IS NOT A PROBLEM, THIS |
| OFFICE WOULD REQUEST ANY REVISIONS TO |
| SPECS/MANUFACTURES CUT SHEET ON FILE BE SUBMITTED FOR |
| REVIEW AND STAMPING. ONE COPY OF REVISED SPECS WOULD |
| STAY ON FILE AND THE OTHER(S) WOULD GO BACK TO JOBSITE. |
| |
| PLEASE BE SURE TO SUBMIT THE SPECS/CUT SHEETS AT THIS |
| TIME FOR REVIEW. |
| 110.3, 90.7 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 6) NOTE: THE PREVIOUS REVIEW GAVE NOTICE TO REQUIRED |
| LIGHTING CONTROLS. THE RESPONSE MENTIONS THIS FACILITY |
| IS A 24HR OCCUPIED LOCATION AND DEVICES WILL BE |
| INSTALLED IN SOME ROOMS ONLY WHICH ARE NOT 24HR USE. |
| PLEASE SHOW ON THE LIGHTING PLANS WHICH ROOMS AND AREAS |
| ARE GOING TO CONTAIN THE AUTOMATED CONTROLS. AT THIS |
| TIME THE PLANS ONLY SHOW STANDARD SWITCHING DEVICES IN |
| ALL LOCATIONS. THE DETAIL FOR OCCUPANCY SENSORS PLACED |
| ON SHEET E-17 DOES NOT SHOW LOCATIONS ON PLANS. |
| PLEASE REVISE LIGHTING PLANS. |
| 13-415.1.ABC.1.1, .1.2, .1.3. |
| ** EXTERIOR LIGHTING IS SHOWN THROUGH * CONTACTOR* WITH |
| PHOTO-SENSOR CONTROL. THIS WILL BE CONFIRMED TO COMPLY |
| WITH FBC 13-415.1.ABC.1.4 |
| |
| 7) NOTE: PLEASE SHOW THE LOCATION AND GROUNDING |
| ELECTRODE ATTACHMENT AND CONDUCTORS FOR THE |
| TRANSFORMERS. THE RESPONSE MENTIONS THE RISER AND E-3 |
| WAS REVISED HOWEVER THIS INFORMATION COULD NOT BE |
| LOCATED?? |
| PLEASE SEE 250.20, 250.30, 250.50, 250.58 AND 250.66 |
| |
| 8) NOTE: PLEASE VERIFY THE STORAGE AREA UPSTAIRS WILL |
| NOT CONTAIN ANY LIGHTING AND WILL ONLY USE THE LIGHTING |
| WHICH IS FROM OPEN AREA AS PLANS DO NOT SHOW ANY LIGHTS |
| AT THIS TIME. |
| FBC 106.1.2 |
| |
| 9) NOTE: PLEASE SHOW THE REQUIRED LEVELS FOR |
| PHOTO-METRICS ON PLANS PER PREVIOUS REVIEW COMMENTS. |
| THESE WERE SUBMITTED IN RESPONSE BOOK. HOWEVER THESE |
| ARE REQUIRED TO BE SHOWN ON PLANS. THE LIGHTING FIXTURE |
| USED FOR EMERGENCY USE ON PLANS ARE NOT THE SAME AS THE |
| FIXTURES SHOWN THE SEPARATE PHOTO-METRICS SHEETS. |
| PLEASE COORDINATE. |
| FAC 61G15-33.004, NFPA-101 7.8.1.3, 7.9.2.2 |
| |
| ** AS STATED ON PREVIOUS AS NOT ALL ITEMS ARE SHOWN AS |
| OF YET THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |