Plan Review Notes
Plan Review Notes For Permit 07090553
Permit Number 07090553
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-13 12:48:49** DENIED **
  
 THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION,
 SECOND REVIEW TOTAL. PLANS WERE ONLY SUBMITTED FOR
 *PLAN REVIEW* FIRST TIME.
  
 ** PLEASE SEE SOME ITEMS ARE STILL IN NEED OF
 ADDRESSING FROM PREVIOUS REVIEW. THERE ARE ALSO SOME
 NEW COMMENTS FOR CHANGES MADE TO PLANS.
  
 1) NOTE: PLEASE BE SURE THE ADDRESS OF THE PROJECT IS
 CORRECTED ON PLANS. THE APPLIED ADDRESS LOCATION AS
 GIVEN ON PREVIOUS REVIEW IS 6255 N JOG RD. HOWEVER THE
 PLANS AND CALCULATIONS NOW HAVE 6527 N JOG RD. IT IS
 UNCLEAR WHERE THIS NEW NUMERICAL DESIGNATION IS COMING
 FROM. THE PERMIT APPLICATION SUBMITTED CONTAINS 6255.
 PLEASE BE SURE TO CORRECT ALL TITLE BLOCKS ON PLANS FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 REVIEWER(S).
 ** PLEASE KNOW THAT ANY SHEETS WHICH DO NOT NEED TO BE
 REPRINTED FOR CORRECTIONS MAY HAVE THE ADDRESS
 CORRECTED BY HAND IN A NEAT FASHION. IF THERE ARE ANY
 QUESTIONS ON THIS PLEASE CALL.
 FAC61G15-23.002, 61G1-16.004, FBC ADMIN SECTIONS
 106.3.5.1.2, 106.5
  
 2) NOTE: PLEASE SEE THE PERMIT APPLICATION SHOWS IN
 DESCRIPTION THE APPLIED SQ FT AS 11,900 SQ FT AND ALSO
 AS 11,900,000 SQ FT. THIS SEEMS TO BE DONE IN ERROR.
 PLEASE KNOW HOWEVER THE ENERGY CALCULATIONS SHOW A SQ
 FT FOR CONDITIONED AND UN-CONDITIONED SPACE AS ONLY
 6120 SQ FT. THE ARCHITECTURAL SHEETS SHOW AS HIGHER SQ
 FOOTAGE THAN THE CALCULATIONS.
 FBC 106.1.2 FOR COORDINATION.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE NOW
 JUST BEING SUBMITTED FOR THE FIRST REVIEW. THE ENERGY
 CALCULATIONS SUBMITTED ARE NOT CODE COMPLIANT IN
 SEVERAL LOCATIONS. COMPONENTS OF THE BUILDING AND
 MECHANICAL SYSTEM ARE NOT COMMENTED ON BY THIS REVIEWER
 ALTHOUGH ALL SYSTEMS ON PLANS ARE REQUIRED TO
 COORDINATE WITH THE SUBMITTED CALCULATIONS AND INPUT
 DATA REPORT. IN THE REMAINDER OF THIS COMMENT THE INPUT
 DATA REPORT WILL BE NOTED AS IDR.
 PLEASE BE SURE ALL LIGHTING ON PLANS IS ACTUALLY PLACED
 INTO THE IDR. THERE ARE SEVERAL ITEMS WHICH ARE NOT
 SHOWN. THE FOLLOWING ARE SOME EXAMPLES GIVEN AS A
 BENEFIT ONLY AND ARE IN NO WAY ALL POSSIBLE ITEMS WHICH
 DO NOT COMPLY. THIS IS NOT AN EXHAUSTED LIST.
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR EXTERIOR LIGHTING. THIS IS BLANK
 WITH NO LIGHTING AT ALL SHOWN. HOW IS THIS POSSIBLE
 WHEN THE PLANS CLEARLY SHOW SEVERAL EXTERIOR FIXTURES?
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR INTERIOR LIGHTING. HOW IS IT
 POSSIBLE THIS SHOWS ONLY THREE TYPES OF FIXTURES WHEN
 THE PLANS CLEARLY SHOW SEVERAL OTHER TYPES AND
 WATTAGES?
 PLEASE SEE THAT ALL LIGHTING ON PLANS AND LIGHTING
 FIXTURE LEGEND COORDINATE WITH THE IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THE SQUARE FOOTAGE AS NOTED ABOVE IN NOTE #2
 DOES NOT COORDINATE WITH PLANS PR PERMIT APPLICATION.
  
 FOR EXAMPLE:
 PLEASE SEE THE METHOD OF CONTROL CAN NOT BE *MANUAL
 ON/OFF? WHEN THERE IS CLEARLY AUTOMATED CONTROLS FOR
 LOCATIONS IN AND OUTSIDE THE BUILDING.
  
 ** AS NOTED ABOVE THIS IS A BRIEF LIST FOR BENEFIT ONLY
 AND IS NOT A LIST OF ALL ITEMS WHICH DO NOT CORRELATE.
 THERE ARE OTHER ITEMS.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2, .1.3, 13-415.2 ETC
  
 4) NOTE: PLEASE SEE THE VERSION OF CALCULATIONS
 SUBMITTED IS REQUIRED TO BE FLA/COM 2.5. PLEASE SEE
 13-400.3.A AS THE VERSION SUBMITTED IS NOT YET ADOPTED
 BY THE FLORIDA BUILDING CODE. THIS HAS BEEN CONFIRMED
 DIRECTLY WITH THE FLORIDA BUILDING COMMISSION.
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING ITEMS AS REQUESTED ON PREVIOUS
 REVIEW. THE RESPONSE LETTER MENTIONS THESE WERE
 VERIFIED FOR LISTING AND SUBMITTED HOWEVER THEY COULD
 NOT BE LOCATED IN ANY DOCUMENTS SUBMITTED. THE RESPONSE
 MENTIONS THE CONTRACTOR MAY CHANGE DURING THE
 CONSTRUCTION PROCESS. THIS IS NOT A PROBLEM, THIS
 OFFICE WOULD REQUEST ANY REVISIONS TO
 SPECS/MANUFACTURES CUT SHEET ON FILE BE SUBMITTED FOR
 REVIEW AND STAMPING. ONE COPY OF REVISED SPECS WOULD
 STAY ON FILE AND THE OTHER(S) WOULD GO BACK TO JOBSITE.
  
 PLEASE BE SURE TO SUBMIT THE SPECS/CUT SHEETS AT THIS
 TIME FOR REVIEW.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: THE PREVIOUS REVIEW GAVE NOTICE TO REQUIRED
 LIGHTING CONTROLS. THE RESPONSE MENTIONS THIS FACILITY
 IS A 24HR OCCUPIED LOCATION AND DEVICES WILL BE
 INSTALLED IN SOME ROOMS ONLY WHICH ARE NOT 24HR USE.
 PLEASE SHOW ON THE LIGHTING PLANS WHICH ROOMS AND AREAS
 ARE GOING TO CONTAIN THE AUTOMATED CONTROLS. AT THIS
 TIME THE PLANS ONLY SHOW STANDARD SWITCHING DEVICES IN
 ALL LOCATIONS. THE DETAIL FOR OCCUPANCY SENSORS PLACED
 ON SHEET E-17 DOES NOT SHOW LOCATIONS ON PLANS.
 PLEASE REVISE LIGHTING PLANS.
 13-415.1.ABC.1.1, .1.2, .1.3.
 ** EXTERIOR LIGHTING IS SHOWN THROUGH * CONTACTOR* WITH
 PHOTO-SENSOR CONTROL. THIS WILL BE CONFIRMED TO COMPLY
 WITH FBC 13-415.1.ABC.1.4
  
 7) NOTE: PLEASE SHOW THE LOCATION AND GROUNDING
 ELECTRODE ATTACHMENT AND CONDUCTORS FOR THE
 TRANSFORMERS. THE RESPONSE MENTIONS THE RISER AND E-3
 WAS REVISED HOWEVER THIS INFORMATION COULD NOT BE
 LOCATED??
 PLEASE SEE 250.20, 250.30, 250.50, 250.58 AND 250.66
  
 8) NOTE: PLEASE VERIFY THE STORAGE AREA UPSTAIRS WILL
 NOT CONTAIN ANY LIGHTING AND WILL ONLY USE THE LIGHTING
 WHICH IS FROM OPEN AREA AS PLANS DO NOT SHOW ANY LIGHTS
 AT THIS TIME.
 FBC 106.1.2
  
 9) NOTE: PLEASE SHOW THE REQUIRED LEVELS FOR
 PHOTO-METRICS ON PLANS PER PREVIOUS REVIEW COMMENTS.
 THESE WERE SUBMITTED IN RESPONSE BOOK. HOWEVER THESE
 ARE REQUIRED TO BE SHOWN ON PLANS. THE LIGHTING FIXTURE
 USED FOR EMERGENCY USE ON PLANS ARE NOT THE SAME AS THE
 FIXTURES SHOWN THE SEPARATE PHOTO-METRICS SHEETS.
 PLEASE COORDINATE.
 FAC 61G15-33.004, NFPA-101 7.8.1.3, 7.9.2.2
  
 ** AS STATED ON PREVIOUS AS NOT ALL ITEMS ARE SHOWN AS
 OF YET THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]