2008-06-05 15:42:07 | BUILDING PLAN REVIEW |
| PERMIT: 07090553 |
| ADD: 6255 N. JOG ROAD |
| CONT: WEST CONSTRUCTION INC. |
| TEL: (561)588-2027 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 6-3-08 |
| REVIEW: 2ST |
| ACTION: DENIED |
| |
| 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) SHEET LS-1 INDICATES THE OCCUPANCY AS A MIXED |
| OCCUPANCY WITH A S-1 MEDIUM HAZARD SECTION. THERE IS NO |
| MEDIUM HAZARD MENTION IN THE CODE, SO PLEASE CHANGE THE |
| INFORMATION ON THE PLANS TO REFLECT THE CORRECT TYPE OF |
| OCCUPANCY; SEE FBC 311 FOR ADDITIONAL INFORMATION. |
| PROVIDE THE MSDS INFORMATION ON ALL TYPES AND QUANTITY |
| OF MATERIALS WHICH WILL BE STORED OR PLACE IN THIS |
| AREA. THE GROSS BUILDING AREA HAS THE NUMBER 17,500 X |
| 3, WHICH TABLE DID THIS NUMBER CAME FROM FOR THE TYPE |
| VB BUILDING? CLARIFY. PLEASE INDICATE THE FLOOD ZONE |
| INFORMATION ON THE PLANS. |
| |
| 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PLEASE |
| PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: (A) ROLL-UP DOORS (B) SHUTTERS |
| (C) WINDOWS (D) INSULATED METAL ROOF PANELS (E) METAL |
| WALL PANELS (F ) HOLLOW METAL DOORS (G) IMPACT GLASS |
| DOOR 106.3.3* PRODUCT PPROVALS- 2004 THOSE PRODUCTS |
| THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 4) SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| 1. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| ANOTHER FORMAT. |
| 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| FAC9B72, WWW.FLORIDABUILDING.ORG. |
| 3. ON THE PRODUCT APPROVAL, MARK WHICH DETAILS APPLY TO |
| THIS JOB. PLEASE USE INK RATHER THAN A HIGHLIGHTER. SEE |
| ADDITIONAL INFORMATION IN PACKAGE. |
| |
| 5) ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| ____ 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION, SEE ATTACHED POLICY: MEAN ROOF HEIGHT/ |
| ROOF PITCH / ROOF DECK TYPE / AREA OF EACH ROOF TYPE |
| ____2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| IN ADDITION TO THE EVALUATION REPORT SUBMITTED, |
| FAC9B72. WWW.FLORIDABUILDING.ORG ____3) |
| FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY YOU ARE |
| USING. ALSO INDICATE WHICH FASTENER IF THE OPTIONS HAVE |
| DIFFERENT PRESSURE LIMITATIONS. ____5) FOR THE FLAT |
| DECK, SPECIFY THE ENHANCED FASTENING FOR CORNER AND |
| PERIMETER ZONES. |
| ___ 6) SEE PRODUCT LIMITATION #7. CALCULATIONS PREPARED |
| BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| |
| 6) FBC 1802. THE SOIL REPORT SUBMITTED BY TIERRA |
| ENGINEERING NEEDS THE ORIGINAL SEAL, CERTIFICATE OF |
| AUTHORIZATION NUMBER AND SIGNATURE OF THE PERSON TAKING |
| RESPONSIBLE FOR THE REPORT. |
| AN ENGINEER PRACTICING THROUGH A DULY AUTHORIZED |
| ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND |
| LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| OF AUTHORIZATION # ON EACH SHEET PER 61G15-23.002 (2) |
| FAC |
| |
| 7) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED. SHEET A-1 FLOOR PLAN IS MISSING THE |
| DIMENSIONS FOR ALL THE ROOMS. |
| |
| 8) SHEET S-3 DETAIL #2; ON THIS SHEET SHOWS THE |
| MEZZANINE PRE-STRESSED PRE-CAST CONCRETE @ 5? O.C AND |
| THE MEZZANINE PLAN SHOWS THEM AT 4? O.C. CLARIFY. |
| |
| 9) 1009.11.5 HANDRAILS SHALL RETURN TO A WALL, GUARD OR |
| THE WALKING SURFACE OR SHALL BE CONTINUOUS TO THE |
| HANDRAIL OF AN ADJACENT STAIR FLIGHT. WHERE HANDRAILS |
| ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| EXTEND HORIZONTALLY AT LEAST 12 INCHES BEYOND THE TOP |
| RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD |
| BEYOND THE BOTTOM RISER. 11-4.9(2) AT THE BOTTOM, THE |
| HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE |
| WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER |
| OF THE EXTENSION SHALL BE HORIZONTAL SEE FIGURE 19C AND |
| 19D. SEE SHEETS S-3 / A-6. |
| |
| 10) FBC 505.1 THE CLEAR HEIGHT ABOVE AND BELOW THE |
| MEZZANINE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN 7 |
| FEET. CLEARLY INDICATE THE HEIGHT BETWEEN THE MEZZANINE |
| FLOOR AND THE CEILING ABOVE. 110.4.2 STORAGE & FACTORY- |
| INDUSTRIAL OCCUPANCIES. THE CALCULATIONS FOR THE |
| MEZZANINE FLOOR LOAD SHALL BE SUBMITTED AND ACCOMPANIED |
| BY AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING |
| THE SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS |
| PER SQ FT. THE COMPUTATIONS & AFFIDAVIT SHALL BE FILED |
| AS A PERMANENT RECORD OF THE BLDG DEPT. |
| |
| 11) PROVIDE THE SHOP DRAWINGS WHICH SHALL INCLUDE ALL |
| ROOFING/ JOIST / ALUMINUM LADDER WITH PLATFORM AND |
| STRUCTURAL DETAILS ETC. FOR THE BUILDING AS STATED ON |
| SHEET S-1, S-2 AND S-5. THE DRAWINGS SHALL BE REVIEWED |
| AND APPROVED BY THE DESIGNER OF RECORD. SHEET S-7 MAKES |
| REFERENCE TO SEE NOTE #6 WHICH IN NOT ON THE SHEET. |
| DETAIL #9 ON SHEET S-7 REQUIRES THE ENGINEERED DESIGN |
| FOR THE OVERHANG. |
| |
| 12) 11-4.4.2 HEAD ROOM. WALKS, HALLS, CORRIDORS, |
| PASSAGEWAYS, AISLES OR OTHER CIRCULATION SPACES SHALL |
| HAVE 80 INCHES MINIMUM CLEAR HEAD ROOM (SEE FIGURE |
| 8(A). IF VERTICAL CLEARANCE OF AN AREA ADJOINING AN |
| ACCESSIBLE ROUTE IS REDUCED TO LESS THAN 80 IN. |
| (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR |
| VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED. (SEE |
| FIGURE 8(C-1). |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |