2008-06-05 15:42:07BUILDING PLAN REVIEW
 PERMIT: 07090553
 ADD: 6255 N. JOG ROAD
 CONT: WEST CONSTRUCTION INC.
 TEL: (561)588-2027
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-3-08
 REVIEW: 2ST
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) SHEET LS-1 INDICATES THE OCCUPANCY AS A MIXED
 OCCUPANCY WITH A S-1 MEDIUM HAZARD SECTION. THERE IS NO
 MEDIUM HAZARD MENTION IN THE CODE, SO PLEASE CHANGE THE
 INFORMATION ON THE PLANS TO REFLECT THE CORRECT TYPE OF
 OCCUPANCY; SEE FBC 311 FOR ADDITIONAL INFORMATION.
 PROVIDE THE MSDS INFORMATION ON ALL TYPES AND QUANTITY
 OF MATERIALS WHICH WILL BE STORED OR PLACE IN THIS
 AREA. THE GROSS BUILDING AREA HAS THE NUMBER 17,500 X
 3, WHICH TABLE DID THIS NUMBER CAME FROM FOR THE TYPE
 VB BUILDING? CLARIFY. PLEASE INDICATE THE FLOOD ZONE
 INFORMATION ON THE PLANS.
  
 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PLEASE
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS: (A) ROLL-UP DOORS (B) SHUTTERS
 (C) WINDOWS (D) INSULATED METAL ROOF PANELS (E) METAL
 WALL PANELS (F ) HOLLOW METAL DOORS (G) IMPACT GLASS
 DOOR 106.3.3* PRODUCT PPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
 1. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.
 3. ON THE PRODUCT APPROVAL, MARK WHICH DETAILS APPLY TO
 THIS JOB. PLEASE USE INK RATHER THAN A HIGHLIGHTER. SEE
 ADDITIONAL INFORMATION IN PACKAGE.
  
 5) ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
 ____ 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION, SEE ATTACHED POLICY: MEAN ROOF HEIGHT/
 ROOF PITCH / ROOF DECK TYPE / AREA OF EACH ROOF TYPE
 ____2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE EVALUATION REPORT SUBMITTED,
 FAC9B72. WWW.FLORIDABUILDING.ORG ____3)
 FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY YOU ARE
 USING. ALSO INDICATE WHICH FASTENER IF THE OPTIONS HAVE
 DIFFERENT PRESSURE LIMITATIONS. ____5) FOR THE FLAT
 DECK, SPECIFY THE ENHANCED FASTENING FOR CORNER AND
 PERIMETER ZONES.
 ___ 6) SEE PRODUCT LIMITATION #7. CALCULATIONS PREPARED
 BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
 6) FBC 1802. THE SOIL REPORT SUBMITTED BY TIERRA
 ENGINEERING NEEDS THE ORIGINAL SEAL, CERTIFICATE OF
 AUTHORIZATION NUMBER AND SIGNATURE OF THE PERSON TAKING
 RESPONSIBLE FOR THE REPORT.
 AN ENGINEER PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION # ON EACH SHEET PER 61G15-23.002 (2)
 FAC
  
 7) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED. SHEET A-1 FLOOR PLAN IS MISSING THE
 DIMENSIONS FOR ALL THE ROOMS.
  
 8) SHEET S-3 DETAIL #2; ON THIS SHEET SHOWS THE
 MEZZANINE PRE-STRESSED PRE-CAST CONCRETE @ 5? O.C AND
 THE MEZZANINE PLAN SHOWS THEM AT 4? O.C. CLARIFY.
  
 9) 1009.11.5 HANDRAILS SHALL RETURN TO A WALL, GUARD OR
 THE WALKING SURFACE OR SHALL BE CONTINUOUS TO THE
 HANDRAIL OF AN ADJACENT STAIR FLIGHT. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER. 11-4.9(2) AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER
 OF THE EXTENSION SHALL BE HORIZONTAL SEE FIGURE 19C AND
 19D. SEE SHEETS S-3 / A-6.
  
 10) FBC 505.1 THE CLEAR HEIGHT ABOVE AND BELOW THE
 MEZZANINE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN 7
 FEET. CLEARLY INDICATE THE HEIGHT BETWEEN THE MEZZANINE
 FLOOR AND THE CEILING ABOVE. 110.4.2 STORAGE & FACTORY-
 INDUSTRIAL OCCUPANCIES. THE CALCULATIONS FOR THE
 MEZZANINE FLOOR LOAD SHALL BE SUBMITTED AND ACCOMPANIED
 BY AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING
 THE SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS
 PER SQ FT. THE COMPUTATIONS & AFFIDAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 11) PROVIDE THE SHOP DRAWINGS WHICH SHALL INCLUDE ALL
 ROOFING/ JOIST / ALUMINUM LADDER WITH PLATFORM AND
 STRUCTURAL DETAILS ETC. FOR THE BUILDING AS STATED ON
 SHEET S-1, S-2 AND S-5. THE DRAWINGS SHALL BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. SHEET S-7 MAKES
 REFERENCE TO SEE NOTE #6 WHICH IN NOT ON THE SHEET.
 DETAIL #9 ON SHEET S-7 REQUIRES THE ENGINEERED DESIGN
 FOR THE OVERHANG.
  
 12) 11-4.4.2 HEAD ROOM. WALKS, HALLS, CORRIDORS,
 PASSAGEWAYS, AISLES OR OTHER CIRCULATION SPACES SHALL
 HAVE 80 INCHES MINIMUM CLEAR HEAD ROOM (SEE FIGURE
 8(A). IF VERTICAL CLEARANCE OF AN AREA ADJOINING AN
 ACCESSIBLE ROUTE IS REDUCED TO LESS THAN 80 IN.
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED. (SEE
 FIGURE 8(C-1).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER