Plan Review Notes
Plan Review Notes For Permit 07090553
Permit Number 07090553
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-01 10:38:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY
  
 1. SHT A-1 ROOM FINISH SCHEDULE FOR ROOMS 113, 115 &
 116. WALLS WITHIN 2 FEET OF WATER CLOSETS & URINALS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE PER
 SECTION 1210.2. EPOXY PAINT OVER GWB IS NOT CONSIDERED
 A HARD SURFACE. PLEASE SHOW COMPLIANCE.
  
 2. SHT A-1 INDICATE TYPE OF WORK WILL BE DONE IN THE
 WORKSHOP AND TYPE AND AMOUNT OF STORAGE IN THE STORAGE
 AREA. SECTION 106.1.2.
  
 3. SHT A-7 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 THE URINAL:
 A. 11-4.18.4 FLUSH CONTROLS (HEIGHT)
 ___FOR LAVS:
 A. 11-4.19.5 FAUCETS
 ___FOR THE SHOWERS:
 A. 11-4.21.3 SEAT HEIGHT
 B. 11-4.21.5 CONTROLS
 C. 11-4.21.7 CURBS (MAX 1/2")
  
 4. SHT A-8 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 SINKS:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED).
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 5. PER SECTION 11-4.1.3(10)(B) WHERE MORE THAN ONE
 DRINKING FOUNTAIN IS PROVIDED, AT LEAST 50% SHALL BE
 ACCESSIBLE. 3 DRINKING FOUNTAINS ARE SHOWN, 2 SHALL BE
 ACCESSIBLE.
  
 6. SHT P-1 THERE IS A NOTE THAT STATES 3" PVC PIPE FOR
 FUTURE USE. SEE CONT. ON CIVIL DRAWINGS. THE PIPE IS
 NOT SHOWN ON THE CIVIL PLANS. PLEASE CLARIFY WHAT THE
 PIPE WILL BE DRAINING AND TO WHERE. SECTION 106.1.2
 (MORE INFORMATION REQUIRED).
  
 7. SHT P-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE STACK WITH THE DRINKING FOUNTAIN AND
 SINK IN THE STORAGE/WORKSHOP AREA SHOWS 3 FIXTURES
 CONNECTING TO THE STACK ON THE FLOOR PLAN, BUT ONLY TWO
 FIXTURES, (P-9 & P-7), ON THE RISER DIAGRAM.--THE
 FLOOR DRAIN IN THE JANITOR ROOM IS NOT SHOWN ON THE
 RISER DIAGRAM BUT IS SHOWN ON THE FLOOR PLAN. PLEASE
 CLARIFY AND CORRELATE THE RISER WITH THE FLOOR PLAN.
 SECTION 106.1.1.
  
 8. SHT P-2 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING. INDICATE THE BACKFLOW ON THE
 WATER RISER DIAGRAM PRIOR TO ENTERING THE BUILDING.
 SECTION 608.13.2.
  
 9. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. INDICATE METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]