2007-11-10 11:24:02REVIEW #: 1ST
 ACTION: DENIED
  
 *NOTE* THIS PLAN SUBMITTED FOR PLAN REVIEW ONLY. NO
 PERMIT APPLICATION HAS BEEN SUBMITTED AT THIS TIME.
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. WALL LOUVERS ARE LISTED AS PANEL WALLS UNDER FAC
 RULE 9B-72 AND AS SUCH A PRODUCT APPROVAL IS REQUIRED.
 PROVIDE PRODUCT APPROVALS FOR EACH TYPE OF WALL LOUVER
 TO BE USED. FOR MORE INFORMATION ON THE FLORIDA PRODUCT
 APPROVAL SYSTEM PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 2. M-1: SUPPLY REGISTERS FOR ELECTRICAL ROOM 107 AND
 MECHANICAL ROOM 108 ARE SHOWN TO BE FED FROM THE RETURN
 DUCT FOR AHU-2. ALSO, THE RETURN GRILL FOR ELECTRICAL
 ROOM 107 IS SHOWN BEING TIED INTO THE SUPPLY BRANCH
 FROM AHU-2 WHICH FEEDS CONFERENCE ROOM 104. PLEASE
 CLARIFY HOW EACH DUCT IS SUPPOSED TO FUNCTION. FBC,M
 603.1 AND FBC 106.1.1
 NOTE: DUE TO THE ABOVE DISCREPANCIES, AIR BALANCES ON
 THESE SYSTEMS CAN NOT BE REVIEWED AT THIS TIME.
  
 3. M-1: SUPPLY AND RETURN DUCTS CROSSING CORRIDOR AT
 ROOMS 109 AND 110 ARE SHOWN WITH 3 OUT OF 4 DUCT
 PENETRATIONS OF WALLS PROTECTED WITH FIRE DAMPERS. ARE
 THESE WALLS INTENDED TO BE FIRE RESISTANCE RATED? THEY
 ARE NOT SHOWN AS SUCH BASED ON THE WALL TYPE AS SHOWN
 ON PAGES A-1 AND A-10. PLEASE COORDINATE THE LOCATIONS
 OF RATED ASSEMBLIES WITH ARCHITECTURAL DESIGNER,
 SHOWING OPENING PROTECTIVES WHERE REQUIRED IN
 ACCORDANCE WITH FBC,M 607.5.
 NOTE: IF IT IS DETERMINED THAT THESE WALLS REQUIRE A
 RATING, SHOW ALL 4 PENETRATIONS TO BE PROTECTED IN
 ACCORDANCE WITH THIS SECTION AND FBC,M 607.8.
  
 4.M-1: EF-3 ON FLOOR PLAN CALLS FOR 690 CFM. FAN
 SCHEDULE ON M-3 SHOWS EF-3 AT 640 CFM. WHICH IS
 CORRECT? VERIFY THAT FAN CAN PROVIDE THE MINIMUM
 VENTILATION AS REQUIRED BY FBC,M TABLE 403.3 FOR LOCKER
 ROOMS, TOILET ROOMS AND SHOWERS. COORDINATE FLOOR PLANS
 WITH EQUIPMENT SCHEDULES.
  
 5. M-2: WHAT IS THE MEANS AND LOCATION OF CONDENSATE
 DISPOSAL? AHU MOUNTING DETAIL SAYS TO SEE PLUMBING
 PLANS FOR CONTINUATION. NO INFORMATION REGARDING
 LOCATION OF CONDENSATE DISCHARGE COULD BE FOUND ON
 PLUMBING PLANS. SHOW CONDENSATE DISPOSAL FOR AHU?S 1,2
 AND 6 TO BE IN COMPLIANCE WITH FBC,M 307.2.1 THROUGH
 307.2.4 AND FBC 1503.6.
  
 6. M-2: FIRE DAMPER DETAIL CALLS FOR ANGLES TO BE
 FASTENED TO SLEEVE PER SMACNA RECOMMENDATIONS. FIRE
 DAMPERS ARE LISTED AND LABELED ASSEMBLIES AND AS SUCH
 SHALL BE INSTALLED PER THEIR LISTING AND MANUFACTURER?S
 INSTALLATION INSTRUCTIONS IN ACCORDANCE WITH FBC,M
 607.2. UNLESS THIS DETAIL MATCHES THE MANUFACTURER?S
 INSTRUCTIONS IT SHOULD BE REMOVED FROM PLANS AND
 REPLACED BY THE MANUFACTURER?S INSTRUCTIONS EITHER ON
 THE PLANS OR AS A SEPARATE SUBMITTAL. IT MAY BE
 REPLACED BY A GENERAL NOTE WHICH DEFERS TO
 MANUFACTURER?S INSTRUCTIONS.
  
 7. M-3: A/C UNIT SCHEDULE, CFM SHOWN ON SCHEDULE FOR
 AHUS DO NOT MATCH THOSE ON FLOOR PLAN. COORDINATE FLOOR
 PLANS AND EQUIPMENT SCHEDULE. ALSO, SEE COMMENT #2
 ABOVE.
  
 8. A/C UNIT SCHEDULE NOTE #3 INDICATES AHU-3 SHALL BE
 OF DOUBLE WALL CONSTRUCTION. NO AHU-3 IS SHOWN ON PLANS
 OR SCHEDULE. PLEASE CLARIFY. FBC 106.1.1.
  
 9. M-3 O.A. SCHEDULE SHOWS AHU-1 SYSTEM DESIGNED FOR
 460 CFM. A/C UNIT SCHEDULE INDICATES AHU-1 TO PROVIDE
 965 CFM OF O.A. WHICH IS CORRECT? PLEASE CLARIFY AND
 COORDINATE SCHEDULES.
  
 10. PROVIDE AN ENERGY CODE COMPLIANCE CERTIFICATION
 FORM (ENERGY CALCULATIONS) IN ACCORDANCE WITH FBC
 13-101.1.1 AND FBC 13-103 (ENTIRE SECTION).
  
 11. COOLING LOAD CALCULATIONS SHALL BE ATTACHED TO THE
 CODE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT AT TIME OF PERMIT APPLICATION IN ACCORDANCE
 WITH FBC 13-407.1.ABC.1 AND ALL HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 FBC 13-407.1.ABC.1.1.
  
 12. AHU?S 1 AND 2 SHALL BE PROVIDED WITH OFF-HOUR
 CONTROLS INCLUDING AUTOMATIC SHUTDOWN, SETBACK
 CONTROLS, OPTIMUM START CONTROLS, SHUTOFF DAMPER
 CONTROLS AND ZONE ISOLATION IN ACCORDANCE WITH FBC
 13-407.1.ABC.2.4.
  
 13. PROVIDE AN AIR BALANCE SCHEDULE SHOWING THE
 BUILDING TO BE PRESSURIZED WITH RESPECT TO THE OUTDOORS
 IN ACCORDANCE WITH FBC 13-409.1.ABC.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: