Plan Review Notes
Plan Review Notes For Permit 07090553
Permit Number 07090553
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-01 10:57:58*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 03.THE PROPOSED FIRE HYDRANTS SHALL BE INSTALLED,
 COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK.
 ADD TO HYDRANT INFORMATION, SHEET C-5.
  
 04.LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS
 TO FIRE PROTECTION EQUIPMENT AND DEVICES.
  
 05.ON THE LIFE SAFETY SHEET (LS-1) IN THE OCCUPANT
 LOAD REFERENCE,THE OCCUPANT LOAD OF 81 LISTED DOES
 NOT CORRELATE WITH 71 AS COMPUTED BY THIS WRITER.
  
 06.SPECIFY THE WALL AND CEILING FINISH MATERIALS FOR
 EXITS, EXIT AISLE CORRIDORS, AND OTHER SPACES IN TERMS
 OF CLASS A, CLASS B, OR CLASS C.
  
 07.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING.AS PER WEST PALM
 BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH.PLEASE BE ADVISED
 THAT THE INSTALLATION OF HURRICANE SHUTTERS SHALL NOT
 OBSCURE OR BLOCK VISIBILITY OF THE ADDRESS NUMBERS.
  
 08.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE
 LOCATION OF THE KNOX BOX.FOR APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 09.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR
 HANDRAILS/GUARD RAILS.
  
 10.ON SHEET A-9 DOOR SCHEDULE NOTE #1 IS UNCLEAR AND
 INCORRECT.CLARIFY BY CHAPTER AND SECTION AS PER
 REFERENCING NFPA 101- 2003 EDITION.
  
 11.SHOW THE LOCATION OF THE FIRE DEPARTMENT
 CONNECTION (FDC).THE FDC SHALL BE EQUIPPED WITH KNOX
 LOCKING CAPS.FOR APPLICATIONS, CONTACT WEST PALM
 BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 12.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE.
  
 13.ON SHEET E-6, THERE ARE TWO EMERGENCY LIGHTS
 ILLUSTRATED ON THE SOUTH WALL OF THE WORKSHOP BUT ONLY
 ONE ILLUSTRATED ON SHEETS LS-1 AND A-2;PLEASE
 CORRELATE THE PLAN SHEETS TO REFLECT SAME LOCATION
 AND/OR NUMBER OF DEVICES.
  
 14.ON SHEET E-6 AND LS-1 THERE IS AN EXIT LIGHT
 ILLUSTARATED IN THE OFFICE AREA HALLWAY BUT IS NOT
 SHOWN ON SHEET A-2;PLEASE CORRELATE THE PLAN SHEETS
 TO REFLECT SAME LOCATION AND/OR NUMBER OF DEVICES.
  
 15.ON SHEET FA-1, DELETE REFERENCE IN NOTE #3 TO THE
 PALM BEACH COUNTY CODE.
  
 16.ON SHEET FA-1, AMEND THE FIRE ALARM SEQUENCE OF
 OPERATIONS TO REFLECT THAT DUCT SMOKE DETECTORS
 INITIATE A GENERAL FIRE ALARM INSTEAD OF A SUPERVISORY
 ALARM.
  
 17.THE NUMBER OF DEVICES ILLUSTRATED FOR ROOM 108 ON
 SHEET FA-2 DOES NOT CORRELATE WITH THE FIRE ALARM RISER
 SHOWN ON THE FA-3 SHEET.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722