2007-11-01 10:57:58 | *****DENIED***** |
| |
| 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 02.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE |
| TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| |
| 03.THE PROPOSED FIRE HYDRANTS SHALL BE INSTALLED, |
| COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK. |
| ADD TO HYDRANT INFORMATION, SHEET C-5. |
| |
| 04.LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS |
| TO FIRE PROTECTION EQUIPMENT AND DEVICES. |
| |
| 05.ON THE LIFE SAFETY SHEET (LS-1) IN THE OCCUPANT |
| LOAD REFERENCE,THE OCCUPANT LOAD OF 81 LISTED DOES |
| NOT CORRELATE WITH 71 AS COMPUTED BY THIS WRITER. |
| |
| 06.SPECIFY THE WALL AND CEILING FINISH MATERIALS FOR |
| EXITS, EXIT AISLE CORRIDORS, AND OTHER SPACES IN TERMS |
| OF CLASS A, CLASS B, OR CLASS C. |
| |
| 07.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| NUMERICAL ADDRESS ON THE BUILDING.AS PER WEST PALM |
| BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN |
| HEIGHT AND NO LESS THAN 1" IN WIDTH.PLEASE BE ADVISED |
| THAT THE INSTALLATION OF HURRICANE SHUTTERS SHALL NOT |
| OBSCURE OR BLOCK VISIBILITY OF THE ADDRESS NUMBERS. |
| |
| 08.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE |
| LOCATION OF THE KNOX BOX.FOR APPLICATIONS, CONTACT |
| WEST PALM BEACH FIRE PREVENTION BUREAU AT |
| 561-804-4724. |
| |
| 09.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR |
| HANDRAILS/GUARD RAILS. |
| |
| 10.ON SHEET A-9 DOOR SCHEDULE NOTE #1 IS UNCLEAR AND |
| INCORRECT.CLARIFY BY CHAPTER AND SECTION AS PER |
| REFERENCING NFPA 101- 2003 EDITION. |
| |
| 11.SHOW THE LOCATION OF THE FIRE DEPARTMENT |
| CONNECTION (FDC).THE FDC SHALL BE EQUIPPED WITH KNOX |
| LOCKING CAPS.FOR APPLICATIONS, CONTACT WEST PALM |
| BEACH FIRE PREVENTION BUREAU AT 561-804-4724. |
| |
| 12.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE |
| REQUIRED ON THE FIRE LINE BACKFLOW DEVICE. |
| |
| 13.ON SHEET E-6, THERE ARE TWO EMERGENCY LIGHTS |
| ILLUSTRATED ON THE SOUTH WALL OF THE WORKSHOP BUT ONLY |
| ONE ILLUSTRATED ON SHEETS LS-1 AND A-2;PLEASE |
| CORRELATE THE PLAN SHEETS TO REFLECT SAME LOCATION |
| AND/OR NUMBER OF DEVICES. |
| |
| 14.ON SHEET E-6 AND LS-1 THERE IS AN EXIT LIGHT |
| ILLUSTARATED IN THE OFFICE AREA HALLWAY BUT IS NOT |
| SHOWN ON SHEET A-2;PLEASE CORRELATE THE PLAN SHEETS |
| TO REFLECT SAME LOCATION AND/OR NUMBER OF DEVICES. |
| |
| 15.ON SHEET FA-1, DELETE REFERENCE IN NOTE #3 TO THE |
| PALM BEACH COUNTY CODE. |
| |
| 16.ON SHEET FA-1, AMEND THE FIRE ALARM SEQUENCE OF |
| OPERATIONS TO REFLECT THAT DUCT SMOKE DETECTORS |
| INITIATE A GENERAL FIRE ALARM INSTEAD OF A SUPERVISORY |
| ALARM. |
| |
| 17.THE NUMBER OF DEVICES ILLUSTRATED FOR ROOM 108 ON |
| SHEET FA-2 DOES NOT CORRELATE WITH THE FIRE ALARM RISER |
| SHOWN ON THE FA-3 SHEET. |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| ADDRESSED |
| |
| |