Date |
Text |
2007-10-15 16:11:29 | **** DENIED **** |
| |
| |
| ** PLAN REVIEW |
| MAINTENANCE BUILDING |
| SOLID WASTE AUTHORITY |
| |
| 1) NOTE: PLEASE KNOW THE PROJECT HAS ONLY BEEN |
| SUBMITTED FOR *PLAN REVIEW* ONLY AND HAS NOT BEEN |
| SUBMITTED FOR PERMIT APPLICATION. |
| PLEASE KNOW ONCE ALL CODE COMMENTS ARE ADDRESSED, PLANS |
| WILL STILL BE IN A FAILED STATUS UNTIL PERMIT |
| APPLICATION IS MADE. |
| ALL VERIFICATION OF LICENSE INFORMATION WILL BE DONE AT |
| THAT TIME. |
| |
| 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| CODES ARE STATED ON PLANS. |
| PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER |
| DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A |
| MINIMUM. |
| PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE |
| REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE |
| FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS |
| FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SEE SOME CODES ON SOME SHEETS ARE NO LONGER |
| IN EFFECT. FOR EXAMPLE, PLEASE SEE FA-1 WHICH |
| REFERENCES THE 2000 LS CODE, 2002 NEC IN NOTES 10 AND |
| 12. |
| PLEASE ALSO SEE NOTES MENTIONS *PALM BEACH COUNTY*, THE |
| ACTUAL LOCATION IS IN THE CITY OF WEST PALM BEACH |
| JURISDICTION. |
| |
| FBC 106.1.2, 110.1.2 ETC. |
| |
| 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS TO COMPLY |
| WITH THE CURRENT FBC AS NOTED ABOVE. |
| PLEASE BE SURE ALL EXTERIOR AND INTERIOR LIGHTING ON |
| PLANS COORDINATE WITH THE INPUT DATA REPORTS. |
| PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415, |
| 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| AS NO ENERGY CALCULATIONS WERE SUBMITTED NO REVIEW CAN |
| BE DONE AT THIS TIME. THERE MAY BE NEW COMMENTS ON THE |
| NEXT REVIEW. |
| FBC 106.1.2 |
| |
| 4) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| .1.4 FOR MISSING LIGHTING CONTROLS REQUIRED. |
| PLEASE INDICATE TIME SCHEDULING IF TIMER CONTROLLED. |
| PLEASE INDICATE OVER RIDE DEVICES. |
| PLEASE INDICATE OVER RIDE MAXIMUM TIMES. |
| **(PLEASE SEE THE MAXIMUM TIMES FOR OCCUPANCY TYPE |
| DEVICES ARE 30MINS AND MAXIMUM FOR TIMER OVER RIDE IS |
| 4HRS) NOTED FOR INFORMATION) |
| |
| 5) NOTE: PLEASE CORRELATE ALL LIGHTING CONTROL DEVICES |
| WITH THE SYMBOL LEGEND. FOR EXAMPLE: PLEASE SEE S WITH |
| THE LETTER DESIGNATIONS IS NOT ALL ON LEGEND. SEE SX IN |
| WOMEN'S TOILET, SEE SU IN JAN'S CLOSET. THESE ARE A FEW |
| AS NOTED. THE COMMENT #4 WILL REQUIRE ADJUSTMENTS |
| ALSO. |
| |
| 6) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR |
| MINIMUM ADA LEVELS FOR ALL HORN AND STROBE DEVICES. |
| PLEASE SEE THE PLANS INDICATE ON LEGEND A *XX* FOR |
| CANDELA LEVELS. PLEASE KNOW THAT ALL LEVELS ARE |
| REQUIRED. PLEASE SEE THERE ARE SEVERAL LOCATIONS ON |
| PLANS IN WHICH LESS THAN 75 CD IS BEING SHOWN. |
| (EXAMPLE: 15, 30) PLEASE SEE .3(4) OF SECTION GIVEN AS |
| THE MINIMUM LEVEL IS 75 CD. |
| PLEASE ADJUST. |
| |
| 7) NOTE: PLEASE ADJUST ALL CIRCUITING ON PANEL |
| SCHEDULE(S) AS THE CIRCUITS ARE REQUIRED TO BE SPECIFIC |
| TO ALL ROOMS AND AREAS IN WHICH THEY FEED. PLEASE KNOW |
| THE GENERAL USE OF *LIGHTING* AND *RECEPTACLES* NEEDS |
| TO BE SPECIFIC. |
| THE ROOMS AND AREAS MAY CONTAIN A NUMERICAL DESIGNATION |
| IF DESIRED. |
| PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| FROM THE NEC. |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.1.2, 110.1.2, 106.1.2 |
| |
| 8) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| FOR THE FOLLOWING ITEMS. |
| ATS, AND GENERATOR TAP BOX. |
| ** PLEASE BE AWARE THERE ARE TAP BOXES ON THE MARKER |
| WHICH THIS AHJ HAS SEEN WHICH ARE NOT LISTED FOR USE, |
| AND WET/OUTDOORLOCATIONS WHEN CONNECTIONS ARE MADE. |
| 90.7, 110.3 |
| FBC 106.1.2 |
| |
| 9) NOTE: PLEASE CLARIFY GENERATOR, AS THE TRANSFER |
| SWITCH BEING INSTALLED IS AN AUTOMATIC DEVICE WHICH |
| LENDS TO A PERMANENTLY INSTALLED GENERATOR HOWEVER |
| COULD NOT LOCATE THIS UNIT ON PLANS. |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 10) NOTE: PLEASE CLARIFY THE MAIN AS SHOWN ON RISER |
| AHEAD OF THE ATS. THIS DISCONNECT SEEMS TO INDICATE A |
| *SHUNT TRIP* PUSH BUTTON OF SOME TYPE FROM A GLASS |
| BREAK. DOES THIS MAIN STILL CONTAIN A MANUAL MEANS OF |
| DISCONNECT RATED FOR THE LOAD SERVED PER 230.76 AND |
| 230.79? |
| 110.3, 90.7 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 11) NOTE: PLEASE CLARIFY THE MAIN CIRCUIT BREAKER FOR |
| PANEL DP. THE RISER CONTAINS A NOTE WHICH MENTIONS THIS |
| IS NOT TO BE SERVICE ENTRANCE RATED? |
| AS THE INSTALLATION OF THE GENERATOR IS NOT CLEAR AT |
| THIS TIME, PLEASE BE SURE TO SEE 225.31-225.39 ALONG |
| WITH 702.11 AS THE DISCONNECTING MEANS FOR THE FEEDERS |
| COMING FROM A GENERATOR NEEDS TO MEET THE SECTIONS AS |
| NOTED ABOVE. |
| PLEASE ALSO CLARIFY THE NOTE ON THE PANEL DP WHICH |
| MENTIONS THIS EQUIPMENT IS: * 800A, 277/480V, |
| *4P*,,,,*.IT IS UNCLEAR WHAT THE 4P IS. IS THE |
| NEUTRAL BEING CONTROLLED BY THIS BREAKER? |
| PLEASE SUBMIT THE SPECS/CUT SHEET FOR THIS EQUIPMENT. |
| 110.3, 90.7 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 12) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE STAIRS |
| UNDER NORMAL AND EMERGENCY USE. PLEASE SEE NFPA-101 |
| 7.8.1.3, AND 7.9.2.2 FOR MINIMUM LEVELS OF 10FT CANDLES |
| UNDER NORMAL AND IS PERMITTED DOWN TO 1FT CANDLE UNDER |
| EMERGENCY. |
| FAC 61G15-33.004 |
| FBC 106.1.2 |
| |
| 13) NOTE: PLEASE SEE THE FOOTING STEEL WHICH IS |
| REQUIRED TO BE PART OF THE GROUNDING ELECTRODE SYSTEM |
| COULD NOT BE LOCATED ON RISER/PLANS PER 250.50. |
| |
| 14) NOTE: PLEASE INDICATE A DETAIL/SHOW LOCATION OF THE |
| TRANSFORMER GROUNDING ELECTRODE SYSTEM PER 250.20, |
| 250.30, AND 250.50 |
| |
| 15) NOTE: PLEASE SEE THE ADDRESS IS MISSING ON |
| PLANS/TITLE BLOCKS PER 61G15-23.002 AND 61G1-16.004. |
| FBC 110.1.2, 106.1.2, 106.3.5 |
| PLEASE KNOW THE ADDRESS LOCATION AS APPLIED FOR AT THE |
| PCN LOCATION PROVIDED ON PLAN REVIEW APPLICATION IS |
| 6255 N. JOG RD. |
| THIS IS NOT YET CONFIRMED AND HAS BEEN ROUTED TO THE |
| ADDRESSING REVIEWER FOR VERIFICATION FOR ACTUAL SITE |
| ADDRESS CONFIRMATION. |
| PLEASE DO NOT BASE ADDRESS ON TITLE BLOCKS UNTIL |
| VERIFIED WITH THE ADDRESSING REVIEWER. |
| |
| 16) NOTE: PLEASE KNOW ALL LOW VOLTAGE AS SHOWN ON PLANS |
| WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. THESE |
| MAY BE USED FOR REFERENCING HOWEVER WILL BE REQUIRED TO |
| PULL SEPARATE PERMITS. |
| THE LV FOR CATV |
| LV FOR SECURITY IS REQUIRED UNDER SEPARATE LV PERMIT |
| FROM CATV, PHONE ETC. |
| ** THIS IS NOTED FOR INFORMATIONAL PURPOSE ONLY AND NO |
| CORRECTIONS OR ADJUSTMENTS TO PLANS ARE NEEDED. |
| |
| 17) NOTE: PLEASE KNOW THE AIC RATINGS SHALL BE SET AND |
| STATED BY THE ENGINEER OF RECORD. THE AVAILABLE FAULT |
| CURRENT SHOULD BE DETERMINED AND SIZING OF EQUIPMENT IS |
| REQUIRED BASED ON THE AVAILABLE FAULT CURRENT. |
| NOTES ON RISER *KEYED NOTES* MENTIONS THIS IS TO BE |
| DONE BY THE ELECTRICAL CONTRACTOR AND THE LEVELS ON |
| PLANS ARE FOR BIDDING PURPOSES ONLY. |
| PLEASE SEE 110.9 NEC. |
| FBC 106.1.2, 106.3.5, ETC AS THE RECORD SETS OF PLANS |
| ARE REQUIRED TOCONTAIN THE ACTUAL INSTALLED AND |
| SPECIFIED. |
| |
| 18) NOTE: PLEASE VERIFY CIRCUITING FOR SITE LIGHTING |
| AS SHOWN ON E-3 WHICH IS CIRCUITED TO H1-6 AND THIS |
| SAME CIRCUIT IS FOR SEVERAL WALL LIGHTING FIXTURES ON |
| BUILDING ON E-6. |
| PLEASE SEE PANEL SCHEDULE ON E-10 MENTIONS WALL |
| LIGHTING ONLY. |
| |
| 19) NOTE: *** IMPORTANT, AS THERE ARE SEVERAL ITEMS NOT |
| YET SUBMITTED FOR REVIEW, REVIEW NOTES ABOVE CAN ONLY |
| BE DONE ON DOCUMENTS AND PLANS SUBMITTED. |
| THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW BASED |
| ON NEW PLANS, CHANGES ETC WHICH CAN NOT BE MADE AT THIS |
| TIME. |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| PLANS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
2007-10-15 13:07:27 | |
| |
| IHN ELEC FOR REVIEW. |