Plan Review Notes
Plan Review Notes For Permit 07090553
Permit Number 07090553
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-15 16:11:29**** DENIED ****
  
  
 ** PLAN REVIEW
 MAINTENANCE BUILDING
 SOLID WASTE AUTHORITY
  
 1) NOTE: PLEASE KNOW THE PROJECT HAS ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW* ONLY AND HAS NOT BEEN
 SUBMITTED FOR PERMIT APPLICATION.
 PLEASE KNOW ONCE ALL CODE COMMENTS ARE ADDRESSED, PLANS
 WILL STILL BE IN A FAILED STATUS UNTIL PERMIT
 APPLICATION IS MADE.
 ALL VERIFICATION OF LICENSE INFORMATION WILL BE DONE AT
 THAT TIME.
  
 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE SOME CODES ON SOME SHEETS ARE NO LONGER
 IN EFFECT. FOR EXAMPLE, PLEASE SEE FA-1 WHICH
 REFERENCES THE 2000 LS CODE, 2002 NEC IN NOTES 10 AND
 12.
 PLEASE ALSO SEE NOTES MENTIONS *PALM BEACH COUNTY*, THE
 ACTUAL LOCATION IS IN THE CITY OF WEST PALM BEACH
 JURISDICTION.
  
 FBC 106.1.2, 110.1.2 ETC.
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS TO COMPLY
 WITH THE CURRENT FBC AS NOTED ABOVE.
 PLEASE BE SURE ALL EXTERIOR AND INTERIOR LIGHTING ON
 PLANS COORDINATE WITH THE INPUT DATA REPORTS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 AS NO ENERGY CALCULATIONS WERE SUBMITTED NO REVIEW CAN
 BE DONE AT THIS TIME. THERE MAY BE NEW COMMENTS ON THE
 NEXT REVIEW.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS REQUIRED.
 PLEASE INDICATE TIME SCHEDULING IF TIMER CONTROLLED.
 PLEASE INDICATE OVER RIDE DEVICES.
 PLEASE INDICATE OVER RIDE MAXIMUM TIMES.
 **(PLEASE SEE THE MAXIMUM TIMES FOR OCCUPANCY TYPE
 DEVICES ARE 30MINS AND MAXIMUM FOR TIMER OVER RIDE IS
 4HRS) NOTED FOR INFORMATION)
  
 5) NOTE: PLEASE CORRELATE ALL LIGHTING CONTROL DEVICES
 WITH THE SYMBOL LEGEND. FOR EXAMPLE: PLEASE SEE S WITH
 THE LETTER DESIGNATIONS IS NOT ALL ON LEGEND. SEE SX IN
 WOMEN'S TOILET, SEE SU IN JAN'S CLOSET. THESE ARE A FEW
 AS NOTED. THE COMMENT #4 WILL REQUIRE ADJUSTMENTS
 ALSO.
  
 6) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR
 MINIMUM ADA LEVELS FOR ALL HORN AND STROBE DEVICES.
 PLEASE SEE THE PLANS INDICATE ON LEGEND A *XX* FOR
 CANDELA LEVELS. PLEASE KNOW THAT ALL LEVELS ARE
 REQUIRED. PLEASE SEE THERE ARE SEVERAL LOCATIONS ON
 PLANS IN WHICH LESS THAN 75 CD IS BEING SHOWN.
 (EXAMPLE: 15, 30) PLEASE SEE .3(4) OF SECTION GIVEN AS
 THE MINIMUM LEVEL IS 75 CD.
 PLEASE ADJUST.
  
 7) NOTE: PLEASE ADJUST ALL CIRCUITING ON PANEL
 SCHEDULE(S) AS THE CIRCUITS ARE REQUIRED TO BE SPECIFIC
 TO ALL ROOMS AND AREAS IN WHICH THEY FEED. PLEASE KNOW
 THE GENERAL USE OF *LIGHTING* AND *RECEPTACLES* NEEDS
 TO BE SPECIFIC.
 THE ROOMS AND AREAS MAY CONTAIN A NUMERICAL DESIGNATION
 IF DESIRED.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE NEC.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 110.1.2, 106.1.2
  
 8) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE FOLLOWING ITEMS.
 ATS, AND GENERATOR TAP BOX.
 ** PLEASE BE AWARE THERE ARE TAP BOXES ON THE MARKER
 WHICH THIS AHJ HAS SEEN WHICH ARE NOT LISTED FOR USE,
 AND WET/OUTDOORLOCATIONS WHEN CONNECTIONS ARE MADE.
 90.7, 110.3
 FBC 106.1.2
  
 9) NOTE: PLEASE CLARIFY GENERATOR, AS THE TRANSFER
 SWITCH BEING INSTALLED IS AN AUTOMATIC DEVICE WHICH
 LENDS TO A PERMANENTLY INSTALLED GENERATOR HOWEVER
 COULD NOT LOCATE THIS UNIT ON PLANS.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 10) NOTE: PLEASE CLARIFY THE MAIN AS SHOWN ON RISER
 AHEAD OF THE ATS. THIS DISCONNECT SEEMS TO INDICATE A
 *SHUNT TRIP* PUSH BUTTON OF SOME TYPE FROM A GLASS
 BREAK. DOES THIS MAIN STILL CONTAIN A MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76 AND
 230.79?
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE CLARIFY THE MAIN CIRCUIT BREAKER FOR
 PANEL DP. THE RISER CONTAINS A NOTE WHICH MENTIONS THIS
 IS NOT TO BE SERVICE ENTRANCE RATED?
 AS THE INSTALLATION OF THE GENERATOR IS NOT CLEAR AT
 THIS TIME, PLEASE BE SURE TO SEE 225.31-225.39 ALONG
 WITH 702.11 AS THE DISCONNECTING MEANS FOR THE FEEDERS
 COMING FROM A GENERATOR NEEDS TO MEET THE SECTIONS AS
 NOTED ABOVE.
 PLEASE ALSO CLARIFY THE NOTE ON THE PANEL DP WHICH
 MENTIONS THIS EQUIPMENT IS: * 800A, 277/480V,
 *4P*,,,,*.IT IS UNCLEAR WHAT THE 4P IS. IS THE
 NEUTRAL BEING CONTROLLED BY THIS BREAKER?
 PLEASE SUBMIT THE SPECS/CUT SHEET FOR THIS EQUIPMENT.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 12) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE STAIRS
 UNDER NORMAL AND EMERGENCY USE. PLEASE SEE NFPA-101
 7.8.1.3, AND 7.9.2.2 FOR MINIMUM LEVELS OF 10FT CANDLES
 UNDER NORMAL AND IS PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY.
 FAC 61G15-33.004
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE THE FOOTING STEEL WHICH IS
 REQUIRED TO BE PART OF THE GROUNDING ELECTRODE SYSTEM
 COULD NOT BE LOCATED ON RISER/PLANS PER 250.50.
  
 14) NOTE: PLEASE INDICATE A DETAIL/SHOW LOCATION OF THE
 TRANSFORMER GROUNDING ELECTRODE SYSTEM PER 250.20,
 250.30, AND 250.50
  
 15) NOTE: PLEASE SEE THE ADDRESS IS MISSING ON
 PLANS/TITLE BLOCKS PER 61G15-23.002 AND 61G1-16.004.
 FBC 110.1.2, 106.1.2, 106.3.5
 PLEASE KNOW THE ADDRESS LOCATION AS APPLIED FOR AT THE
 PCN LOCATION PROVIDED ON PLAN REVIEW APPLICATION IS
 6255 N. JOG RD.
 THIS IS NOT YET CONFIRMED AND HAS BEEN ROUTED TO THE
 ADDRESSING REVIEWER FOR VERIFICATION FOR ACTUAL SITE
 ADDRESS CONFIRMATION.
 PLEASE DO NOT BASE ADDRESS ON TITLE BLOCKS UNTIL
 VERIFIED WITH THE ADDRESSING REVIEWER.
  
 16) NOTE: PLEASE KNOW ALL LOW VOLTAGE AS SHOWN ON PLANS
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. THESE
 MAY BE USED FOR REFERENCING HOWEVER WILL BE REQUIRED TO
 PULL SEPARATE PERMITS.
 THE LV FOR CATV
 LV FOR SECURITY IS REQUIRED UNDER SEPARATE LV PERMIT
 FROM CATV, PHONE ETC.
 ** THIS IS NOTED FOR INFORMATIONAL PURPOSE ONLY AND NO
 CORRECTIONS OR ADJUSTMENTS TO PLANS ARE NEEDED.
  
 17) NOTE: PLEASE KNOW THE AIC RATINGS SHALL BE SET AND
 STATED BY THE ENGINEER OF RECORD. THE AVAILABLE FAULT
 CURRENT SHOULD BE DETERMINED AND SIZING OF EQUIPMENT IS
 REQUIRED BASED ON THE AVAILABLE FAULT CURRENT.
 NOTES ON RISER *KEYED NOTES* MENTIONS THIS IS TO BE
 DONE BY THE ELECTRICAL CONTRACTOR AND THE LEVELS ON
 PLANS ARE FOR BIDDING PURPOSES ONLY.
 PLEASE SEE 110.9 NEC.
 FBC 106.1.2, 106.3.5, ETC AS THE RECORD SETS OF PLANS
 ARE REQUIRED TOCONTAIN THE ACTUAL INSTALLED AND
 SPECIFIED.
  
 18) NOTE: PLEASE VERIFY CIRCUITING FOR SITE LIGHTING
 AS SHOWN ON E-3 WHICH IS CIRCUITED TO H1-6 AND THIS
 SAME CIRCUIT IS FOR SEVERAL WALL LIGHTING FIXTURES ON
 BUILDING ON E-6.
 PLEASE SEE PANEL SCHEDULE ON E-10 MENTIONS WALL
 LIGHTING ONLY.
  
 19) NOTE: *** IMPORTANT, AS THERE ARE SEVERAL ITEMS NOT
 YET SUBMITTED FOR REVIEW, REVIEW NOTES ABOVE CAN ONLY
 BE DONE ON DOCUMENTS AND PLANS SUBMITTED.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW BASED
 ON NEW PLANS, CHANGES ETC WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2007-10-15 13:07:27 
  
 IHN ELEC FOR REVIEW.