2007-10-29 11:40:30 | CONSTRUCTION SERVICES DEPARTMENT |
| 200 SECOND STREET, 3RD FLOOR, |
| WEST PALM BEACH, FLORIDA33401 |
| TEL:561-805-6713FAX:561-805-6731 |
| |
| JAMES JOHNSTON, |
| BUILDING PLAN EXAMINER II |
| E-MAIL:JJOHNSTON @WPB.ORG |
| |
| |
| |
| |
| BASIC WIND SPEED ? MPH140 |
| |
| PERMIT NO 07090553 |
| PROJECTMAINTENANCE FACILITY SOLID WASTE ADDRESS |
| 6255 N JOG ROAD |
| |
| DATE10/26/07 |
| |
| |
| BUILDINGPLANREVIEW |
| |
| FLORIDA BUILDING CODES 2004 |
| |
| 1 |
| PROJECT INFORMATION SHEETLS-1 |
| FBCBUILDING503 |
| TYPE OF CONSTRUCTION V - B |
| THEB OCCUPANCY IS RATED V-B |
| S-1 OCCUPANCY IS RATEDV-B |
| COMMENT-PLEASE NOTE ON SHEETLS-1 |
| |
| |
| 1-A |
| WPB AMENDMENTS TO FBC 2004 EDITION |
| BASIC WIND SPEED |
| 117.1 BASIC WIND SPEED. THE CITY OF WEST PALM BEACH |
| FALLS ENTIRELY IN THE 140 MPH REGION COMMENT-THE |
| BASIC WIND SPEED IS 140 MPH |
| PLEASE NOTE ON SHEETLS-1 |
| |
| |
| 1-B |
| FBCBUILDING1604.5 |
| WIND IMPORTANCE FACTORII |
| COMMENT- |
| PLEASE NOTE ON SHEETLS-1 |
| |
| 1-C |
| FBCBUILDING 1604.5 |
| WIND EXPOSURE |
| COMMENT- |
| PLEASE NOTE ON SHEETLS-1 |
| |
| |
| 2 |
| FBCBUILDING1802.6SOIL TEST REPORT |
| THE SOIL CLASSIFICATION AND DESIGN LOAD-BEARING |
| CAPACITY |
| SHALL BE SHOWN ON THE CONSTRUCTION DOCUMENT. |
| WHERE REQUIRED BY THE BUILDING OFFICIAL, A WRITTEN |
| REPORT |
| OF THE INVESTIGATION SHALL BE SUBMITTED THAT INCLUDES, |
| BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION: |
| COMMENT-PLEASE SUBMIT THE SOIL TEST REPORT FOR THIS |
| PROJECT |
| |
| |
| 3 |
| WPB ADMENDMENT109.3.4 TERMITES. BUILDING COMPONENTS |
| AND BUILDING SURROUNDINGS REQUIRED TO BE PROTECTED FROM |
| TERMITE DAMAGE IN ACCORDANCE WITH SECTION 1503.6, |
| SECTION 2304.13 OR SECTION 2304.11.6, SPECIFICALLY |
| REQUIRED TO BE INSPECTED FOR TERMITES IN ACCORDANCE |
| WITH SECTION 2114, OR REQUIRED TO HAVE CHEMICAL SOIL |
| TREATMENT IN ACCORDANCE WITH SECTION 1816 SHALL NOT BE |
| COVERED OR CONCEALED UNTIL THE RELEASE |
| FROM THE BUILDING OFFICIAL HAS BEEN RECEIVED COMMENT |
| PLEASE PROVIDE THIS INFORMATION ON DRAWINGS |
| |
| |
| 4 |
| FLORIDA STATUE713.13NOTICE OF COMMENCEMENT FILE |
| NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. IF |
| THE |
| WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED WITHIN |
| 90 |
| DAYS OF FILING THE NOTICE WILL BECOME NULL AND VOID. |
| SUBMIT THE NOTICE AT THE TIME OF PERMIT ISSUANCE AND |
| POST A COPY AT THE JOB SITE BEFORE THE FIRST |
| INSPECTION. |
| COMMENT-FOR YOUR INFORMATION |
| |
| |
| 5 |
| FBC BUILDING504.2 AUTOMATIC SPRINKLER SYSTEM |
| INCREASE. |
| THIS CHAPTER OF THE CODE ALLOWS THE BUILDING HEIGHT TO |
| BE INCREASED BY 20? AND THE MAXIMUM NO. OF STORIES |
| INCREASE BY ONE STORY |
| COMMENT-FOR YOUR INFORMATION TYPE OF |
| |
| |
| 5-A |
| FBC BUILDING506.3 AUTOMATIC SPRINKLER SYSTEM |
| INCREASE |
| |
| COMMENT- |
| AREA INCREASE WITH AUTOMATIC SPRINKLER SYSTEM IS 300 |
| PERCENT FOR SINGLE STORY BUILDING |
| COMMENT-FOR YOUR INFORMATION |
| |
| 6 |
| PRODUCT APPROVALS REQUIRED |
| FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 |
| REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS |
| SUBMIT TWO COPIES OF EACH APPROVAL |
| ( 3 COPIES IF A THRESHOLD BUILDING ) WITH FLORIDA |
| PRODUCT |
| APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S |
| SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR |
| KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH |
| THE PLANS AND SPECIFICATIONS. |
| SEE:WEB SITEWWW.FLORIDABUILDING.COM |
| |
| ALUMINUM WINDOWS |
| FIXED GLASS |
| MULLION TUBES |
| ALUMINUM OUT -SWING DOORS |
| HOLLOW METAL DOORS |
| EXTERIOR GLAZED DOORS |
| HURRICANE SHUTTERS |
| LOUVERS,NO REPORT SUBMITTED |
| ROLL UP DOOR |
| COMMENT-PLEASE PROVIDE THE FOLLOWING FLORIDA PRODUCT |
| APPROVALS |
| |
| |
| 7 |
| FBC BUILDING1609.6 SIMPLIFIED WIND LOAD METHOD. |
| 1609.1 APPLICATIONS. |
| BUILDINGS, STRUCTURES AND PARTS THEREOF SHALL BE |
| DESIGNED |
| TO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED HEREIN. |
| |
| COMMENT-PLEASEPROVIDE THE DESIGN PRESSURE FOR THE |
| WINDOWS AND DOORS, GARAGE DOORS, LOUVERS, MULLIONS |
| |
| |
| 8 |
| WPB AMENDMENTS TO FBC 2004 EDITION |
| 110.4.2 STORAGE AND FACTORY-INDUSTRIAL OCCUPANCIES. IT |
| SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPRIETOR OR OCCUPANT OF GROUP S WHERE EXCESSIVE FLOOR |
| LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| ARCHITECT OR ENGINEER IN COMPUTING THE SAFE LOAD |
| CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| SAFE ALLOWABLE FLOOR LOAD ON EACH FLOOR IN POUNDS PER |
| SQUARE FOOT UNIFORMLY DISTRIBUTED |
| 110.4.3 SIGNS REQUIRED. |
| COMMENTIN EVERY BUILDING OR PART OF A BUILDING A SAFE |
| FLOOR LOAD SHALL BE POSTED IN A CONSPICUOUS LOCATION. |
| THIS SECTION REFERS TO THE MEZZANINE. PLEASE |
| FURNISH THE SAFE LOAD CAPACITY AND NOT ON PLAN THE |
| REQUIRED INFORMATION TO BE POSTED AT THE MEZZANINE. |
| |
| |
| 9 |
| FBC BUILDING 2200 |
| THE FOLLOWING INFORMATION IS PROVIDED FOR |
| REVIEW BY THE DESIGNER OF RECORD, THE |
| SPECIALITY ENGINEER, AND THE PROJECT |
| ENGINEER |
| |
| |
| 10 |
| FBC BUILDING2223.5.3 |
| COMMENT THE MANUFACTURER SHALL DESIGN THE METAL SYSTEM |
| BUILDING AND/OR COMPONENT SYSTEM IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 16 |
| METAL BUILDING STRUCTURAL DESIGN, PANEL WALLS INSULATED |
| PANEL CEILING, PRE-ENGINEERED METAL CANOPY |
| COMMENT-PLEASE PROVIDE THE SPECIAL ENGINEERING?S |
| DESIGN AND SPECIFICATIONS FOR THE METAL BUILDING |
| COMPONENTS |
| |
| |
| 10-A |
| FBC BUILDING2223.4.1 |
| COMMENT -THE STRUCTURAL ENGINEER OF RECORD AND/OR THE |
| ARCHITECTOF RECORD SHALL REQUIRE STRUCTURAL |
| SUBMITTALS FOR REVIEW |
| AS AN INDICATION THAT HIS OR HER INTENT HAS BEEN |
| UNDERSTOOD |
| AND THAT THE SPECIFIED CRITERIA HAVE BEEN USED. THE |
| STRUCTURAL SUBMITTALS SHALL BEAR THE IMPRESSED SEAL, |
| SIGNATURE AND DATE OF THE SPECIALTY ENGINEER WHO |
| PREPARED THEM. |
| |
| 10-B |
| FBC BUILDING2222.4.8 |
| METAL SIDING AND ROOF PANELS SHALL BE DESIGNED, WHERE |
| POSSIBLE, TO BE CONTINUOUS OVER TWO OR MORE SPANS. |
| COMMENT PLEASESUBMIT THE METAL BUILDING SPECIALTY |
| ENGINEERING DESIGN FOR PLAN REVIEW COMPLIANCE NOTING |
| THE INFORMATION PROVIDEDHEREIN |
| |
| |
| 10-C |
| FBC BUILDING2223.5.1 |
| COMMENT CALCULATIONS FOR DRIFT AND DEFLECTION OF THE |
| METAL |
| SYSTEM BUILDING SHALL BE BY THE SPECIALTY ENGINEER. |
| |
| |
| 10-D |
| FBC BUILDING2223.8.4 |
| STRUCTURAL STANDING-SEAM ROOF SHEETS SHALL BE A |
| MINIMUM |
| OF 24 GAUGE [0.0239 INCH (.6 MM) NOMINAL] IN THICKNESS |
| COMMENT FOR YOUR INFORMATION |
| |
| 10-E |
| FBC BUILDING2223.8.5 |
| DIRECT SCREW ATTACHED ROOF AND WALL SHEETS MAY BE USED |
| AS |
| DIAPHRAGMS PROVIDED THE SHEETS ARE A MINIMUM OF 24 |
| GAUGE |
| COMMENTFOR YOUR INFORMATION |
| |
| 10-F |
| 2222.4.3 |
| FBC BUILDINGMETAL SIDING AND ROOF PANELS SHALL BE |
| NOT |
| |
| LESS THAN 24 GAUGE. |
| COMMENTFOR YOUR INFORMATION |
| |
| |
| 10-G |
| 2222.4.5 |
| FBC BUILDINGTHE BENDING STRESS OF METAL SIDING AND |
| ROOF |
| PANELS SHALL BE DESIGNED USING A SAFETY FACTOR OF NOT |
| LESS |
| THAN 2.5. |
| COMMENT FOR YOUR INFORMATION |
| |
| 11 |
| FBC BUILDING 1600 LOADS |
| COMMENT PLEASE VERIFY THE SUSPENDED GYPSUM CEILING |
| SUPPORTED BY THE METAL ROOF STRUCTURE SYSTEM |
| COMPONENTS |
| WILL CARRY THE LOAD IMPOSED BY THIS CEILING SYSTEM. |
| THIS WILL BE REFLECTED IN THE STRUCTURAL DESIGN BY THE |
| METAL |
| BUILDING MANUFACTURER?SSPECIALTY ENGINEER |
| |
| |
| 12 |
| FBC BUILDING CHAPTER 11 ACCESSIBILITY |
| 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW |
| CONSTRUCTION |
| SHEETC-1COMMENT PLEASE PROVIDE A DETAIL FOR THE |
| 5? |
| |
| WIDE HANDICAP ACCESSIBLE ISLE FROM THE PARKING LOT TO |
| THE |
| SIDEWALK WITH A LEVEL CONNECTION |
| |
| |
| 13 |
| FLORIDA BUILDING CODE BUILDING 1210.2 WALLS. COMMENT |
| PLEASE NOTE ON PLAN.. WALLS WITHIN 2 FEET OF URINALS |
| AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE |
| FLOOR |
| |
| |
| 14 |
| FLORIDA BUILDING CODE BUILDING 713.1 GENERAL - FIRE |
| RESISTANT JOINT SYSTEM |
| COMMENTOCCUPANCY SEPARATION WALL. JOINTS |
| INSTALLED |
| |
| IN OR BETWEEN FIRE-RESISTANCE-RATED, WALLS,FLOOR OR |
| FLOOR/CEILING |
| ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| BE |
| PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE |
| |
| 15 |
| FBC BUILDING1207.2AIR-BORNE SOUND. |
| COMMENTWALLS, PARTITIONS AND FLOOR/CEILING |
| ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC |
| OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| |
| (STC) OF NOT LESS THAN 50 |