Plan Review Notes For Permit 07090546 |
Permit Number |
07090546 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-10-17 14:43:45 | | | *** PROVISO/REVISION NEEDED ***** | | | | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH STILL | | NEEDS TO BE ADDRESSED. | | THIS HAS BEEN SET UP AS A *PROVISO* WHICH WILL REQUIRE | | REVISIONS *BEFORE* ROUGH ELECTRICAL INSPECTION. | | | | 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW, THE | | FOLLOWING CODES SHALL BE STATED ON THE ELECTRICAL PLANS | | FOR MINIMUM RELEVANT CODE DESIGN. | | FBC 2004 W/2006 REVS? | | 2005 NFPA-70 (NEC). | | 2003 NFPA-101 | | | | 2) NOTE: PLEASE SEE THE TWO NEW OFFICE ROOMS BEING | | CREATED NEED TO HAVE LIGHTING CONTROLS TO MEET 13-101, | | 13-415.1.ABC.1, 13-415.1.ABC.1.2. | | (TIMER TYPE DEVICES, MAXIMUM OF 4HRS, OCCUPANCY TYPE | | DEVICES 30MINS) | | | | 3) NOTE: PLEASE SUBMIT A REVISED PANEL SCHEDULE AND | | LOADS FOR NEW CIRCUITS. | | 220, 215.5, 408.4, 310.16, 240.4, | | FBC 106.3.5.1.2, 106.1.2 | | | | ** AS STATED ON PREVIOUS REVIEW: | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS | | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. | | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY | | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, | | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND | | THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|