Plan Review Notes
Plan Review Notes For Permit 07090546
Permit Number 07090546
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-17 14:43:45 
 *** PROVISO/REVISION NEEDED *****
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH STILL
 NEEDS TO BE ADDRESSED.
 THIS HAS BEEN SET UP AS A *PROVISO* WHICH WILL REQUIRE
 REVISIONS *BEFORE* ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW, THE
 FOLLOWING CODES SHALL BE STATED ON THE ELECTRICAL PLANS
 FOR MINIMUM RELEVANT CODE DESIGN.
 FBC 2004 W/2006 REVS?
 2005 NFPA-70 (NEC).
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE TWO NEW OFFICE ROOMS BEING
 CREATED NEED TO HAVE LIGHTING CONTROLS TO MEET 13-101,
 13-415.1.ABC.1, 13-415.1.ABC.1.2.
 (TIMER TYPE DEVICES, MAXIMUM OF 4HRS, OCCUPANCY TYPE
 DEVICES 30MINS)
  
 3) NOTE: PLEASE SUBMIT A REVISED PANEL SCHEDULE AND
 LOADS FOR NEW CIRCUITS.
 220, 215.5, 408.4, 310.16, 240.4,
 FBC 106.3.5.1.2, 106.1.2
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]