Plan Review Notes
Plan Review Notes For Permit 07090546
Permit Number 07090546
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-28 19:24:552007-09-28 19:24:55
  
 ** DENIED **
  
 CORRECTIONS/ADJUSTMENTS NEEDED.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THE ABOVE ARE NOTED ON PLANS.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, 13-103 AS THE NEW
 LIGHTING CONTROL DEVICES BEING REPLACED NEED TO CONTAIN
 AUTOMATED CONTROL.(MAXIMUM OF 30MINS FOR OCCUPANCY TYPE
 DEVICES AND 4HRS FOR TIMERS).
  
 3) NOTE: PLEASE INDICATE THE CIRCUITING FOR NEW
 RECEPTACLES/LIGHTS AND TO WHICH PANEL THESE WILL BE FED
 FROM.
 PLEASE CLARIFY SIZE OF CONDUCTORS AND CIRCUIT
 AMPERAGE.
 PLEASE CLARIFY IF THIS SPACE IS ONE TENANT. THIS SEEMS
 TO BE THE CASE HOWEVER THIS IS NOT COMPLETELY CLEAR AT
 THIS TIME.
  
 ** PLEASE KNOW, IF ALL OTHER TRADES PASS THEIR REVIEW,
 A *PROVISO* MAY BE CONSIDERED FOR ISSUANCE OF PERMIT AS
 THE ABOVE ITEMS COULD BE ADJUSTED AND SUBMITTED AS A
 REVISION BEFORE ROUGH.
 THIS IS ONLY IF ALL OTHER TRADES PASS REVIEWS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  