Plan Review Notes
Plan Review Notes For Permit 07090529
Permit Number 07090529
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-20 09:25:24PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE DONE BY FORM 400A-04R
 V.2.5, SEE FBC 13-400.3.A. PLEASE CORRECT.
  
 2) WHEN SUBMITTING CORRECTED ENERGY CALCULATIONS SEE
 (IMPORTANT NOTE) ON FRONT PAGE REGARDING INPUT REPORT
 PRINT-OUT, PLEASE COMPLY.
  
 3) WHEN SUBMITTING CORRECTED ENERGY CALCULATIONS THEY
 WILL NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER 2004
 FBC 13-400.3.ABC.2.
  
 4) ENERGY CALCULATIONS PAGE 4 SHOW SYSTEM 2 AS 14 SEER,
 MECHANICAL PLAN SHOWS IT AS A 13 SEER, THE TWO MUST
 COINCIDE. PLEASE CORRECT.
  
 5) THE N.O.A. FOR THE A/C CONDENSER STAND EXPIRED ON
 5/14/07. PLEASE CORRECT.
  
 6) MECHANICAL PLAN EQUIPMENT SCHEDULE NEEDS TO SHOW THE
 MANUFACTURER'S NAME.
  
 7) I COULD NOT FIND THE A/C SYSTEMS ON THE ARI
 DIRECTORY WEB-SITE, PLEASE SUBMIT ARI DIRECTORY PAGE
 FOR A/C SYSTEMS.
  
 8) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS AND SHOW
 OUTDOOR AIR IS BEING SUPPLIED TO THE SPACE ON
 MECHANICAL PLAN,SEE MECH. 403.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]