Plan Review Notes For Permit 07090519 |
Permit Number |
07090519 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-06-20 08:11:51 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLAN. | | *** DENIED *** | | | | 1) THE MECHANICAL PLAN ON FILE IS SIGNED AND SEALED BY | | AN ARCHITECT (STEPHEN M. ROY) SO ONLY HE CAN MAKE | | REVISIONS TO THEM, PER FAC 61G1-16.003. | | | | 2) THE ENERGY CALCULATIONS WILL NEED TO BE REVISED AS | | THE AIR HANDLER IS NOW INSTALLED IN THE GARAGE, PER | | 2004 FBC 13-600.3.ABC.2. PLEASE SUBMIT WITH PLAN | | REVISION. | | | | 3) SHOW ON THE MECHANICAL PLAN HOW RETURN AIR IS | | GETTING BACK TO THE AIR HANDLER, PER 2004 FBC/R | | M1602.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|