 *** REDLINED PLANS***
  
 1) THE CONDUIT AND CONDUCTORS FROM METER TO MAIN
 BREAKER PANEL SHALL BE INSTALLED UNDERGROUND/IN SLAB.
 230.70, 230.71.
 IF THIS IS NOT DONE, A MAIN WITH OVER CURRENT
 PROTECTION WILL BE REQUIRED OUTSIDE ALONG WITH AN
 EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 2)KITCHEN WALL AS NOTED ON PREVIOUS REVIEW MUST MEET
 210.52 FOR RECEPTACLE SPACING. RECEPTACLE SHOWN IS NOT
 WITHIN 6FT OF DOOR WAY.
  
 3) PLANS SHOW TWO GARAGE DOOR OPENERS HOWEVER PANEL
 SCHEDULE ONLY SHOWS ONE CIRCUIT.
 PLEASE SEE 430.248 AS THE HP RATING OF EACH MOTOR MAY
 REQUIRE TWO SEPARATE CIRCUITS BEING DEDICATED.
  
 4) LOW VOLTAGE SHOWN ON PLAN REQUIRES A SEPARATE
 PERMIT. PLANS SHOW PHONE AND CATV ONLY.
 MAY REFERENCE THESE PLANS FOR CATV AND PHONE.
 ANY OTHER SYSTEMS INSTALLED (IE: ) SPEAKERS, WILL
 REQUIRED PLANS/LAYOUT OF LOCATIONS.
  