Plan Review Notes For Permit 07090519 |
Permit Number |
07090519 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-12-06 14:31:05 | DENIED; | | 1. THE ARCHITECTURE FURM IS REQUIRED TO SHOW CORPS. | | CERTIFICATION NUMBER IN TITLE BLOCK. FBC BUILDING | | SECTION 106.1. | | 2.BATHROOM AND 1/2 BATH DOWN STREAM OF THE KITCHEN | | NOT VENTED TO CODE. SEE FBC PLUMBING SECTION 909.1. THE | | SINKS CANNOT GO THREW THE BATHROOM GROUP. | | 3. THE AUTOMATIC CLOTHES WASHER IS STILL NOT VENTED. | | SHOW VENT ON SANITARY RISER DIAGRAM. ( SEE ONE P.1 PAGE | | IS MARKED IN RED) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|