Plan Review Notes
Plan Review Notes For Permit 07090519
Permit Number 07090519
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-20 15:49:15** DENIED 2ND REVIEW **
  
 ** PLEASE KNOW AS PLANS ARE ONLY NOW BEING COMPLETED
 AND SUBMITTED FOR ELECTRICAL REVIEW THERE ARE SEVERAL
 NEW COMMENTS. THESE COMMENTS COULD NOT HAVE BEEN MADE
 ON PREVIOUS PLANS SUBMITTED..
  
 1) NOTE:PLEASE COMPLETE TITLE BLOCKS WITH LICENSE
 INFORMATION AND ADDRESS INFORMATION WHICH COORDINATES
 WITH THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
 PLEASE SEE IT SEEMS THE LAST NUMBER OF THE LICENSE
 NUMBER IS NOT BEING PRINTED ON SHEETS. THIS COULD HAVE
 BEEN REDLINED, HOWEVER PLANS WERE COMING BACK FOR OTHER
 COMMENTS.
 PLEASE SEE THE ADDRESS ON THE STATE SITE DOES NOT
 CORRELATE. (743 BISCAYNE ?)
  
 2) NOTE: PLEASE SEE PLANS NOW INDICATE AND NEW SERVICE
 HOWEVER PLEASE SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON PLANS.
 WE ARE UNABLE TO DETERMINE CODE COMPLIANCE WITH MANY
 ITEMS WITHOUT THESE SHOWN ON PLANS.
 110.26, 240.24, 230.70, 230.71 ETC
  
 3) NOTE: PLEASE SEE THE SCALE ON ELECTRICAL PLANS IS
 BEING SHOWN AS QUARTER INCH PER FOOT; HOWEVER THIS DOES
 NOT CORRELATE WITH THE REST OF THE PLANS/SHEETS. PLEASE
 SEE MECHANICAL PLANS FOR EXAMPLE AS THE SAME SCALE IS
 SHOWN YET THE LAYOUT IS SUBSTANTIALLY DIFFERENT.
 PLEASE KNOW THAT REVIEW FOR SOME ITEMS SUCH AS
 RECEPTACLE SPACING CAN NOT BE DONE AT THIS TIME.
 FBC 106.3.5.4, 106.3.1, 106.1
  
 4) NOTE: PLEASE SEE 210.52 AS SOME RECEPTACLES ARE
 MISSING FOR RULING.
 PLEASE SEE KITCHEN WALL FOR EXAMPLE WHERE NO
 RECEPTACLES ARE BEING SHOWN. (ONE LOCATION NOTED
 ONLY).
  
 5) NOTE: PLEASE SEE RISER SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR FROM THE NEW METER TO THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 240.24, 250.6.
  
 6)NOTE: PLEASE SEE MISSING LOAD FOR DINING AS
 REQUIRED PER 210.52B1, 220.53.
 PLEASE SEE THAT ONE OR *MORE* OF THE REQUIRED CIRCUITS
 EACH REQUIRE 1500VA.
  
 7) NOTE: PLEASE SEE 220.54 AS THE MINIMUM VA FOR THE
 DRYER SHALL BE 5KVA.
 (PLANS SHOW 4).
  
 8) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON
 PLANS. SOME ITEMS CAN NOT BE REVIEWED FOR CODE
 COMPLIANCE AT THIS TIME.
  
 9) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOAD
 CALCULATIONS ARE MISSING THE REQUIRED DEDICATED
 CIRCUIT(S) FOR GDO/ GARAGE DOOR OPENERS.
 430.148, 310.16, 240.4, 220.
 FBC 106.1.2
  
 10) NOTE: PLEASE VERIFY 350MCM FOR SERVICE ENTRANCE
 CONDUCTORS. THIS IS NOT A CODE ISSUE HOWEVER IF SHOWN
 AS 350MCM ON PLANS, THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED. THIS IS ONLY NOTED FOR INFORMATION ONLY.
  
 11) NOTE: PLEASE MAKE NOTE FOR SECTION OF FBC
 13-606.1.ABC.1.2.4 FOR TYPE OF RECESSED LIGHTING
 FIXTURES.
  
 12) NOTE: PLEASE SEE THERE ARE SOME LIGHTING FIXTURES
 ON PLANS WHICH DO NOT INDICATE ANY CONTROLS.
 PLEASE SEE FOR EXAMPLE WHAT APPEAR TO BE MASTER BEDROOM
 LIGHTS.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE 210.8A2 FOR REQUIRED GFI
 RECEPTACLES IN GARAGE.
 MISSING GFI DESIGNATION(S).
  
 14) NOTE: PLEASE SEE 210.8A3 AS ALL RECEPTACLES OUTSIDE
 ARE ALSO REQUIRED TO BE GFI. PLEASE SEE MISSING
 DESIGNATIONS.
  
 15) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING
 RECEPTACLE(S) PER 210.52C2 AND 4.
 PLEASE SEE THIS IS FOR WHAT IS SHOWN AS A SECOND
 ISLAND.
 PLEASE CLARIFY THE RECEPTACLE AS SHOWN. THIS IS SHOWN
 IN SINK OR UNDER SINK.
 THIS LOCATION, WALL, COUNTER SPACE IS UNCLEAR AT THIS
 TIME.
  
 ** PLEASE KNOW AS SOME ITEMS WERE NOT SHOWN AT THIS
 TIME, SOME ITEMS COULD NOT BE DETEMINED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  