Date |
Text |
2007-11-20 15:49:15 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE KNOW AS PLANS ARE ONLY NOW BEING COMPLETED |
| AND SUBMITTED FOR ELECTRICAL REVIEW THERE ARE SEVERAL |
| NEW COMMENTS. THESE COMMENTS COULD NOT HAVE BEEN MADE |
| ON PREVIOUS PLANS SUBMITTED.. |
| |
| 1) NOTE:PLEASE COMPLETE TITLE BLOCKS WITH LICENSE |
| INFORMATION AND ADDRESS INFORMATION WHICH COORDINATES |
| WITH THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| REGULATION. |
| PLEASE SEE IT SEEMS THE LAST NUMBER OF THE LICENSE |
| NUMBER IS NOT BEING PRINTED ON SHEETS. THIS COULD HAVE |
| BEEN REDLINED, HOWEVER PLANS WERE COMING BACK FOR OTHER |
| COMMENTS. |
| PLEASE SEE THE ADDRESS ON THE STATE SITE DOES NOT |
| CORRELATE. (743 BISCAYNE ?) |
| |
| 2) NOTE: PLEASE SEE PLANS NOW INDICATE AND NEW SERVICE |
| HOWEVER PLEASE SHOW THE LOCATION OF THE SERVICE |
| EQUIPMENT ON PLANS. |
| WE ARE UNABLE TO DETERMINE CODE COMPLIANCE WITH MANY |
| ITEMS WITHOUT THESE SHOWN ON PLANS. |
| 110.26, 240.24, 230.70, 230.71 ETC |
| |
| 3) NOTE: PLEASE SEE THE SCALE ON ELECTRICAL PLANS IS |
| BEING SHOWN AS QUARTER INCH PER FOOT; HOWEVER THIS DOES |
| NOT CORRELATE WITH THE REST OF THE PLANS/SHEETS. PLEASE |
| SEE MECHANICAL PLANS FOR EXAMPLE AS THE SAME SCALE IS |
| SHOWN YET THE LAYOUT IS SUBSTANTIALLY DIFFERENT. |
| PLEASE KNOW THAT REVIEW FOR SOME ITEMS SUCH AS |
| RECEPTACLE SPACING CAN NOT BE DONE AT THIS TIME. |
| FBC 106.3.5.4, 106.3.1, 106.1 |
| |
| 4) NOTE: PLEASE SEE 210.52 AS SOME RECEPTACLES ARE |
| MISSING FOR RULING. |
| PLEASE SEE KITCHEN WALL FOR EXAMPLE WHERE NO |
| RECEPTACLES ARE BEING SHOWN. (ONE LOCATION NOTED |
| ONLY). |
| |
| 5) NOTE: PLEASE SEE RISER SHOWS AN EQUIPMENT GROUNDING |
| CONDUCTOR FROM THE NEW METER TO THE FIRST MEANS OF |
| DISCONNECT WHICH IS NOT PERMITTED. |
| PLEASE SEE 240.24, 250.6. |
| |
| 6)NOTE: PLEASE SEE MISSING LOAD FOR DINING AS |
| REQUIRED PER 210.52B1, 220.53. |
| PLEASE SEE THAT ONE OR *MORE* OF THE REQUIRED CIRCUITS |
| EACH REQUIRE 1500VA. |
| |
| 7) NOTE: PLEASE SEE 220.54 AS THE MINIMUM VA FOR THE |
| DRYER SHALL BE 5KVA. |
| (PLANS SHOW 4). |
| |
| 8) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON |
| PLANS. SOME ITEMS CAN NOT BE REVIEWED FOR CODE |
| COMPLIANCE AT THIS TIME. |
| |
| 9) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOAD |
| CALCULATIONS ARE MISSING THE REQUIRED DEDICATED |
| CIRCUIT(S) FOR GDO/ GARAGE DOOR OPENERS. |
| 430.148, 310.16, 240.4, 220. |
| FBC 106.1.2 |
| |
| 10) NOTE: PLEASE VERIFY 350MCM FOR SERVICE ENTRANCE |
| CONDUCTORS. THIS IS NOT A CODE ISSUE HOWEVER IF SHOWN |
| AS 350MCM ON PLANS, THIS IS WHAT WILL BE REQUIRED TO BE |
| INSTALLED. THIS IS ONLY NOTED FOR INFORMATION ONLY. |
| |
| 11) NOTE: PLEASE MAKE NOTE FOR SECTION OF FBC |
| 13-606.1.ABC.1.2.4 FOR TYPE OF RECESSED LIGHTING |
| FIXTURES. |
| |
| 12) NOTE: PLEASE SEE THERE ARE SOME LIGHTING FIXTURES |
| ON PLANS WHICH DO NOT INDICATE ANY CONTROLS. |
| PLEASE SEE FOR EXAMPLE WHAT APPEAR TO BE MASTER BEDROOM |
| LIGHTS. |
| FBC 106.1.2 |
| |
| 13) NOTE: PLEASE SEE 210.8A2 FOR REQUIRED GFI |
| RECEPTACLES IN GARAGE. |
| MISSING GFI DESIGNATION(S). |
| |
| 14) NOTE: PLEASE SEE 210.8A3 AS ALL RECEPTACLES OUTSIDE |
| ARE ALSO REQUIRED TO BE GFI. PLEASE SEE MISSING |
| DESIGNATIONS. |
| |
| 15) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING |
| RECEPTACLE(S) PER 210.52C2 AND 4. |
| PLEASE SEE THIS IS FOR WHAT IS SHOWN AS A SECOND |
| ISLAND. |
| PLEASE CLARIFY THE RECEPTACLE AS SHOWN. THIS IS SHOWN |
| IN SINK OR UNDER SINK. |
| THIS LOCATION, WALL, COUNTER SPACE IS UNCLEAR AT THIS |
| TIME. |
| |
| ** PLEASE KNOW AS SOME ITEMS WERE NOT SHOWN AT THIS |
| TIME, SOME ITEMS COULD NOT BE DETEMINED. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |