Plan Review Notes For Permit 07090519 |
Permit Number |
07090519 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-24 09:12:52 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) MECHANICAL PLAN PAGE M.1 THE BUILDING AND ROOM | | LAY-OUT IS FADED AND DIFFICULT TO READ, PLEASE CORRECT. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, SEE F.B.C. | | 106.1.1. | | | | 2) NEED TO SHOW THE SIZE AND CFM'S FOR THE SUPPLY AIR | | GRILL IN THE FAMILY ROOM. | | | | 3) SUBMIT ENERGY CALCULATIONS, SEE FBC 13.101.2. | | | | 4)SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 FBC | | 13-607.1.ABC.1. | | | | 5)SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL DUCT | | DESIGN, SEE 2004 FBC/R M1601.1 AND FBC 13-610.1.ABC.1. | | | | 6) THE ARCHITECT NEEDS TO SIGN AND SEAL THE PLANS, SEE | | F.A.C. 61G1-16.003. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] | | |
|