Plan Review Notes
Plan Review Notes For Permit 07090519
Permit Number 07090519
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-24 09:12:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN PAGE M.1 THE BUILDING AND ROOM
 LAY-OUT IS FADED AND DIFFICULT TO READ, PLEASE CORRECT.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, SEE F.B.C.
 106.1.1.
  
 2) NEED TO SHOW THE SIZE AND CFM'S FOR THE SUPPLY AIR
 GRILL IN THE FAMILY ROOM.
  
 3) SUBMIT ENERGY CALCULATIONS, SEE FBC 13.101.2.
  
 4)SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.1.
  
 5)SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL DUCT
 DESIGN, SEE 2004 FBC/R M1601.1 AND FBC 13-610.1.ABC.1.
  
 6) THE ARCHITECT NEEDS TO SIGN AND SEAL THE PLANS, SEE
 F.A.C. 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  