Plan Review Notes
Plan Review Notes For Permit 07090519
Permit Number 07090519
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-23 09:40:44 
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THAT ALL THREE SETS OF PLANS
 SUBMITTED ARE PHOTO-COPIES AND ARE NOT ORIGINAL SIGNED,
 DATED AND SEALED PLANS AS REQUIRED PER FS 481.221.
 ** PLEASE KNOW THAT FOR A SINGLE FAMILY DWELLING ONLY
 TWO SIGNED, DATED AND SEALED SETS ARE NEEDED.
 IF A THIRD SET IS DESIRED FOR STAMPING/DUPLICATE, THEN
 A THIRD SET OF SIGNED, DATED AND SEALED PLANS MAY BE
 PROVIDED FOR STAMPING.
  
 3) NOTE: PLEASE ADJUST AND COMPLETE TITLE BLOCK WITH
 ALL LICENSE INFORMATION NEEDED. PLEASE SEE TITLE BLOCKS
 STILL INDICATE MR. LITTLE. THIS REVIEWER HAS BEEN IN
 CONTACT WITH MR. ROY FOR REQUIRED
 INFORMATION/ADJUSTMENTS.
 FAC 61G1-16.004, FS 481.219.
  
 4) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR
 REVIEW FOR CODE COMPLIANCE WITH THE PREVIOUS NOTED
 CODES ABOVE. PLEASE SEE NFPA-70 (NEC 2005) AND
 NFPA-72.
 ALL THREE SETS DO NOT CONTAIN ELECTRICAL PLANS. FBC
 106.1.2, 106.1.3, 106.3.5.4
 PLEASE PROVIDE PANEL SCHEDULE(S) WITH ALL MINIMUM
 REQUIRED CIRCUITS PER NEC. 408.4, 240.4, 310.16,
 210.52, 210.11, 220, 215.5 ETC
 PLEASE PROVIDE ALL CONDUCTOR SIZES IN PANEL(S) ALONG
 WITH CONDUCTORS SIZES.240.4, 310.16
 PLEASE PROVIDE A RISER DIAGRAM FOR NEW OR EXISTING
 PROPOSED SERVICE COMPLETE WITH ALLCONDUCTOR SIZES,
 CONDUITS, FEEDERS, GROUNDING, AIC RATINGS AND OVER
 CURRENT PROTECTION DEVICES.
 230.70, 230.71, 1100.9, 230.72, 230.76, 230.79, 310.16,
 250.50, 240.4 ETC
 PLEASE PROVIDE ALL SMOKE ALARM LOCATIONS INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS PER NFPA-72 11.5.1.1,
 11.8.3. FBC R313, FBC 905.2, ETC.
 PLEASE PROVIDE ALL RECEPTACLE LOCATIONS REQUIRED PER
 ALL OF 210.52
 PLEASE PROVIDE ALL LIGHTING AND CONTROL LOCATIONS PER
 210.70, LS 101 7.8.
 PLEASE BE SURE TO PROVIDE LISTING OF ALL ARC FAULT
 PROTECTED CIRCUITS PER 210.12.
 PLEASE PROVIDE ALL DISCONNECTING MEANS FOR EQUIPMENT AS
 REQUIRED. 440.11, 422.30, 422.31.
 PLEASE PROVIDE LOAD CALCULATIONS FOR ALL ELECTRICAL
 FROM NEW OR EXISTING SERVICE. NEC 220.**PLEASE BE SURE
 TO SEE THE NEW 2005 CODE WITH RESPECT TO WATER HEATERS
 TO BE FIGURED AT 125% PER 422.13.
 PLEASE SUBMIT ENERGY CALCULATIONS PER FBC CHAPTER 13.
 PLEASE BE SURE TO REFERENCE ANY RECESSED LIGHTING PER
 FBC 13-606.1.ABC.1.2.4 FOR *AIR MOVEMENT* ALLOWANCES
 FROM CONDITIONED SPACE.
  
 ** PLEASE SEE SOME OF THE ITEMS REFLECT ABOVE ARE IN NO
 WAY ALL ITEMS IN THE NEC WHICH WILL BE REVIEWED.
 THE ITEMS ABOVE ARE FOR ITEMS NEEDED, AS EACH DWELLING
 AND SCOPE OF WORK VARIES AND PLANS WERE NOT SUBMITTED
 FOR REVIEW IT IS NOT POSSIBLE TO GIVE CODE COMPLIANT
 REVIEW AT THIS TIME.
 PLEASE KNOW THERE MAY VERY WELL BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH COULD NOT BE MADE AT THIS TIME.
 **IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  