2007-09-28 16:39:37 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| |
| ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| EACH ROOF TYPE |
| |
| _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG.THE TILE |
| AND POLYFOAM NOAS ARE NO LONGER IN THE PACKAGE.THE |
| FLORIDA STATE PRODUCT APPROVAL REQUIREMENT INCLUDES THE |
| FLORIDA STATE PRODUCT APPROVAL COVER SHEET, |
| INSTALLATION INSTRUCTIONS AND EVALUATION REPORT. |
| |
| _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| LIMITATIONS. THE ASSEMBLY SELECTED REFERS TO GENERAL |
| LIMITATION #9, WHICH DOES NOT ALLOW ENHANCED FASTENING. |
| THIS SYSTEM HAS A PRESSURE LIMITATION OF -45PSF; -89 |
| MINIMUM REQUIRED FOR CORNER ZONES. |
| |
| _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| SHEET). THIS WAS PREVIOUSLY REQUESTED BUT WAS NOT |
| ADDRESSED. THE PRODUCT YOU SELECTED REQUIRES FOR THIS |
| TO BE DONE BY AN ENGINEER, ARCHITECT, OR REGISTERED |
| ROOF CONSULTANT. |
| |
| ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| |
| _XX_ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| |