2007-12-07 08:32:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE THREE TON A/C SYSTEM IS TO LARGE. COOLING LOAD
 CALCULATIONS ARE CALLING FOR 25,086 TOTAL COOLING
 BTU'S. MECHANICAL PLANS ARE SHOWING 33,600 TOTAL
 COOLING BTU'S. THE PLANS CAN ONLY CALL FOR 15% MORE
 BTU'S. THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-607.1.ABC.1.1. A 2.5 TON SYSTEM MAY MEET YOUR NEEDS,
 SEE ATTACHED ARI CERTIFICATE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]