2007-11-02 15:48:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATION ARE SHOWING THE UNDER AIR
 AREA AS 918 SQUARE FEET AND THE CEILING HEIGHT AS 10
 FEET, THE BUILDING PLANS STATE THE UNDER AIR AREA AS
 828 SQUARE FEET AND THE CEILING HEIGHT AS 8 FOOT 4
 INCHES. PLEASE CORRECT THE COOLING LOAD CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]