Plan Review Notes
Plan Review Notes For Permit 07090501
Permit Number 07090501
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-27 11:30:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 FBC 13-600.3.A. OR YOU MAY SUBMIT FORM 600C-04R, SEE
 2004 FBC 13-101.2.3.
  
 2) ENERGY CALCULATIONS LINE #1 SHOWS CONSTRUCTION AS
 ADDITION, PLEASE CORRECT TO EXISTING OR RENOVATION, SEE
 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 11A SHOWS THE SUPPLY AIR
 DUCTS ARE IN A CONDITIONED SPACE, MECHANICAL PLANS SHOW
 THE SUPPLY AIR DUCTS TO BE IN ATTIC, PLEASE CORRECT
 ENERGY CAL'S.
  
 4) COOLING LOAD CALCULATIONS (MANUAL J) ARE CALLING FOR
 25,559 TOTAL BTU'S, THE A/C SYSTEM BEING INSTALLED ON
 THE MECHANICAL PLAN IS 33,600 TOTAL BTU'S. THE PLANS
 CAN ONLY CALL FOR 15% MORE TOTAL BTU'S THAN THE COOLING
 LOAD CAL'S, SEE FBC 13-607.1.ABC.1.1. (SEE ATTACHED ARI
 LISTING, PERHAPS A 2.5 TON SYSTEM WOULD MEET THE
 REQUIREMENTS). PLEASE CORRECT.
  
 5) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]