| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING |
| CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC |
| AS |
| AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE |
| FOLLOWING: |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| FS, RESPECTIVELY. |
| THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| IF EXEMPTIONS APPLY. |
| |
| 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| EXISTING BUILDING CODE. DECLARE SAME ON THE PLAN. |
| |
| 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| |
| 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE PLAN |
| TO INDICATE COMPLIANCE. |
| |
| 5} REGARDING THE AHU IN THE BATHROOM PER 240.24(E) IN |
| DWELLING UNITS AND GUEST ROOMS OR GUEST SUITES OF |
| HOTELS AND MOTELS, OVERCURRENT DEVICES, OTHER THAN |
| SUPPLEMENTARY OVERCURRENT PROTECTION, SHALL NOT BE |
| LOCATED IN BATHROOMS. |
| |
| 6} LOCATE THE CONDENSING UNIT ON THE PLAN. ALSO SHOW |
| COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14, |
| RECEPTACLE PER 210.63. ALSO NOTE ZONING WILL NEED TO |
| SEE THE LOCATION FOR SETBACK REQUIREMENTS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| [email protected] |