 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING
 CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC
 AS
 AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. DECLARE SAME ON THE PLAN.
  
 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE PLAN
 TO INDICATE COMPLIANCE.
  
 5} REGARDING THE AHU IN THE BATHROOM PER 240.24(E) IN
 DWELLING UNITS AND GUEST ROOMS OR GUEST SUITES OF
 HOTELS AND MOTELS, OVERCURRENT DEVICES, OTHER THAN
 SUPPLEMENTARY OVERCURRENT PROTECTION, SHALL NOT BE
 LOCATED IN BATHROOMS.
  
 6} LOCATE THE CONDENSING UNIT ON THE PLAN. ALSO SHOW
 COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14,
 RECEPTACLE PER 210.63. ALSO NOTE ZONING WILL NEED TO
 SEE THE LOCATION FOR SETBACK REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  