2007-09-27 11:14:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE |
| FBC 13-600.3.A. OR YOU MAY SUBMIT FORM 600C-04R, SEE |
| 2004 FBC 13-101.2.3. |
| |
| 2) WHEN RESUBMITTING ENERGY CALCULATIONS HAVE ADDRESS |
| AND OTHER REQUIRED INFORMATION ON FRONT PAGE, SEE |
| YELLOW HIGH LIGHTS ON OLD ENERGY CALCULATIONS. SEE |
| W.P.B. AMEND. 106.1.3. |
| |
| 3) ENERGY CALCULATIONS LINE #1 SHOWS CONSTRUCTION AS |
| NEW, PLEASE CORRECT TO EXISTING OR RENOVATION, SEE FBC |
| 13-600.3.ABC.2. |
| |
| 4) ENERGY CALCULATIONS LINE 11A SHOWS THE SUPPLY AIR |
| DUCTS ARE IN A CONDITIONED SPACE, MECHANICAL PLANS SHOW |
| THE SUPPLY AIR DUCTS TO BE IN ATTIC, PLEASE CORRECT |
| ENERGY CAL'S. |
| |
| 5) COOLING LOAD CALCULATIONS (MANUAL J) ARE CALLING FOR |
| 19,168 TOTAL BTU'S, THE A/C SYSTEM BEING INSTALLED ON |
| THE MECHANICAL PLAN IS 28,000 TOTAL BTU'S. THE PLANS |
| CAN ONLY CALL FOR 15% MORE TOTAL BTU'S THAN THE COOLING |
| LOAD CAL'S, SEE FBC 13-607.1.ABC.1.1.PLEASE CORRECT. |
| |
| 6) MECHANICAL PLANS, THE SUPPLY AIR DUCT TO THE KITCHEN |
| NEEDS TO BE SIZED, SEE W.P.B. AMEND. 106.3.5.4 (10). |
| PLEASE CORRECT. |
| |
| 7) THE MECHANICAL PLANS NEED THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND |
| CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE |
| W.P.B. AMEND. 106.1.3. |
| |