2007-09-27 11:14:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 FBC 13-600.3.A. OR YOU MAY SUBMIT FORM 600C-04R, SEE
 2004 FBC 13-101.2.3.
  
 2) WHEN RESUBMITTING ENERGY CALCULATIONS HAVE ADDRESS
 AND OTHER REQUIRED INFORMATION ON FRONT PAGE, SEE
 YELLOW HIGH LIGHTS ON OLD ENERGY CALCULATIONS. SEE
 W.P.B. AMEND. 106.1.3.
  
 3) ENERGY CALCULATIONS LINE #1 SHOWS CONSTRUCTION AS
 NEW, PLEASE CORRECT TO EXISTING OR RENOVATION, SEE FBC
 13-600.3.ABC.2.
  
 4) ENERGY CALCULATIONS LINE 11A SHOWS THE SUPPLY AIR
 DUCTS ARE IN A CONDITIONED SPACE, MECHANICAL PLANS SHOW
 THE SUPPLY AIR DUCTS TO BE IN ATTIC, PLEASE CORRECT
 ENERGY CAL'S.
  
 5) COOLING LOAD CALCULATIONS (MANUAL J) ARE CALLING FOR
 19,168 TOTAL BTU'S, THE A/C SYSTEM BEING INSTALLED ON
 THE MECHANICAL PLAN IS 28,000 TOTAL BTU'S. THE PLANS
 CAN ONLY CALL FOR 15% MORE TOTAL BTU'S THAN THE COOLING
 LOAD CAL'S, SEE FBC 13-607.1.ABC.1.1.PLEASE CORRECT.
  
 6) MECHANICAL PLANS, THE SUPPLY AIR DUCT TO THE KITCHEN
 NEEDS TO BE SIZED, SEE W.P.B. AMEND. 106.3.5.4 (10).
 PLEASE CORRECT.
  
 7) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729