Plan Review Notes
Plan Review Notes For Permit 07090500
Permit Number 07090500
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-26 16:12:04 
  
 APPLICATION # 07090500
 ELECTRICAL PLAN REVIEW
 1386 9TH COURT
  
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING
 CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC
 AS
 AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS,PANEL SCHEDULES,
 SERVICE EQUIPMENT AND PANEL LOCATIONS PER 106.3.5.4
 FBC. 215.5NEC. NOTE #6 INDICATES A SERVICE TO A NEW
 SHED, INCLUDE ON THE RISER DIAGRAM. PHYSICALLY LOCATE
 ALL SERVICE EQUIPMENT ON THE PLAN.
  
 3} SHOW THE LOCATION OF THE A/C CONDENSER ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE COMPLIANCE IN THE
 PANEL SCHEDULE.
  
 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. INDICATE
 COMPLIANCE ON THE PLAN.
  
 6} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  