2007-10-08 17:35:23 | |
| |
| DENIED |
| |
| 1)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE. |
| THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG. |
| WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE |
| DENIED. ****PLEASE SEE ONE COPY OF ATTACHED COVER |
| SHEETS FOR STORM PANELS AND SINGLE HUNG WINDOWS**** |
| |
| 2)PRODUCT APPROVALS ARE REQUIRED FOR PGT MULLIONS |
| (FL# 261-R3) WHERE TWO OR MORE WINDOW UNITS ARE |
| ATTACHED TOGETHER |
| |
| 3)THE NOA FOR THE EXTERIOR DOORS WAS SUBMITTED WITH |
| THE INCORRECT DRAWINGS THAT BELONG TO IT PLEASE NOTE |
| THAT THE MIAMI-DADE REPORT IS FOR GLAZED DOORS AND THEY |
| HAVE NO IMPACT RATING AND WOULD THEREFORE REQUIRE |
| SHUTTERS. THE FLORIDA STATEWIDE PRODUCT APPROVAL # FOR |
| JELD WEN O/S STEEL DOORS WITH WOOD EDGES IS (FL# |
| 539-R3) AND THE MIAMI-DADE REPORT # 02-0712.06 |
| |
| 4)THE MIAMI-DADE REPORT FOR THE STORM PANELS HAS ALSO |
| BEEN REVISED SEE THE ATTACHED UPDATED REPORT, PLEASE |
| NOTE THAT THE ANCHOR SPACINGS HAVE CHANGED. |
| |
| 5)SHUTTER SPANS ON THE INSTALLATION SCHEDULE ARE |
| INCORRECT SPAN = OPENING HEIGHT (IF APPLIED VERTICALLY) |
| PLUS 2 X E.D. (7") EG. OPENING # 1 |
| 5'-3" + 7" SPAN = 5'-10" OR 70" PLEASE NOTE THAT 3 1/2" |
| IS THE ED IF 3" IS USED THE ANCHOR SPACING WILL BE |
| REDUCED BY MULTIPLYING BY THE FACTOR |
| ON PAGE 7 OF 9 IN NOA |
| |
| 6)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| PLEASE MAKE CORRECTIONS TO PRODUCT APPROVALS AND |
| SHUTTER INSTALLATION SCHEDULE AND RESUBMIT |
| |