2007-10-08 17:35:23 
  
 DENIED
  
 1)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED. ****PLEASE SEE ONE COPY OF ATTACHED COVER
 SHEETS FOR STORM PANELS AND SINGLE HUNG WINDOWS****
  
 2)PRODUCT APPROVALS ARE REQUIRED FOR PGT MULLIONS
 (FL# 261-R3) WHERE TWO OR MORE WINDOW UNITS ARE
 ATTACHED TOGETHER
  
 3)THE NOA FOR THE EXTERIOR DOORS WAS SUBMITTED WITH
 THE INCORRECT DRAWINGS THAT BELONG TO IT PLEASE NOTE
 THAT THE MIAMI-DADE REPORT IS FOR GLAZED DOORS AND THEY
 HAVE NO IMPACT RATING AND WOULD THEREFORE REQUIRE
 SHUTTERS. THE FLORIDA STATEWIDE PRODUCT APPROVAL # FOR
 JELD WEN O/S STEEL DOORS WITH WOOD EDGES IS (FL#
 539-R3) AND THE MIAMI-DADE REPORT # 02-0712.06
  
 4)THE MIAMI-DADE REPORT FOR THE STORM PANELS HAS ALSO
 BEEN REVISED SEE THE ATTACHED UPDATED REPORT, PLEASE
 NOTE THAT THE ANCHOR SPACINGS HAVE CHANGED.
  
 5)SHUTTER SPANS ON THE INSTALLATION SCHEDULE ARE
 INCORRECT SPAN = OPENING HEIGHT (IF APPLIED VERTICALLY)
 PLUS 2 X E.D. (7") EG. OPENING # 1
 5'-3" + 7" SPAN = 5'-10" OR 70" PLEASE NOTE THAT 3 1/2"
 IS THE ED IF 3" IS USED THE ANCHOR SPACING WILL BE
 REDUCED BY MULTIPLYING BY THE FACTOR
 ON PAGE 7 OF 9 IN NOA
  
 6)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 PLEASE MAKE CORRECTIONS TO PRODUCT APPROVALS AND
 SHUTTER INSTALLATION SCHEDULE AND RESUBMIT
  
 BLDG PLAN REVIEW