Plan Review Notes
Plan Review Notes For Permit 07090474
Permit Number 07090474
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-01 10:24:13DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 OR
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SHEET 2 EQUIPMENT LAYOUT IS INDICATING A 2 INCH
 RETURN TO JETS AND A 2 INCH MAIN DRAIN LINE TO PUMP "B"
 BUT THE LEGEND IS INDICATING PUMP "C" AS BEING USED.
 THIS IS CONFUSING, ARE THERE ONE OR TWO PUMPS BEING
 USED? PLEASE CLARIFY OR CORRELATE THIS ON THE
 RESUBMITTAL PER FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]