 BUILDING PLAN REVIEW
 PERMIT: 07090466
 ADD: 1041 45TH STREET
 CONT: NEUTRON ELECTRIC
 TEL: (561)201-5005
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 3-10-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE 2007 REVISIONS.
  
 2) 3RDREQUEST, MISSING INFORMATION ON PLAN IN REGARDS
 TO WIND: 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS, 1)- BASIC WIND SPEED, MPH 2)-
 WIND IMPORTANCE FACTOR, & BUILDING CATEGORY3)- WIND
 EXPOSURE
  
 3) 3RDREQUEST,2004 FBC 1609.1.3 PLEASE PROVIDE
 INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST
 THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING.
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE SIZE
 OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL
 COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE
 DESIGNER. FL.S .S 481.229 (ARCHITECT) OR FL.S.S 471.003
 (ENGINEER). THIS AREA IS IN A FLOOD ZONE AH; THEREFORE
 THE ELEVATION OF THE CONCRETE SHALL BE A MINIMUM OF
 17'6", WHICH SHALL BE STATED OF THE ENGINEERED PLANS.
 ALL DIMENSIONS FOR THE CONCRETE SLAB SHALL BE INDICATED
 ON THE DRAWINGS INCLUDING THE THICKNESS. INDICATE THE
 CLEARANCE AROUND THE GENERATOR FOR MAINTENANCE AND
 REPAIR WORK.
  
 **NOTE** IN ORDER TO PROVIDE CONFORMITY TO OUR RECORD
 RETENTION PROGRAM 'NO WHITE-OUT OR HANDWRITING IN PEN
 OR PENCIL' ON THE DRAWINGS OR REPORTS WILL BE
 ACCEPTABLE. CLEARLY STATE IF THE GENERATOR IS USED FOR
 LIFE SAFETY ISSUES.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)805-6676
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved