2008-03-10 15:33:02 | |
| 1041 45TH ST 2ND REV.DOC |
| BUILDING PLAN REVIEW |
| PERMIT: 07090466 |
| ADD: 1041 45TH STREET |
| CONT: NEUTRON ELECTRIC |
| TEL: (561)201-5005 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 3RD 3-10-08 |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM |
| BEACH ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME |
| REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| 2004 FBC BUILDING WITH THE 2007 REVISIONS. |
| |
| 2) 3RDREQUEST, MISSING INFORMATION ON PLAN IN REGARDS |
| TO WIND: 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE |
| CONSTRUCTION DRAWINGS, 1)- BASIC WIND SPEED, MPH 2)- |
| WIND IMPORTANCE FACTOR, & BUILDING CATEGORY3)- WIND |
| EXPOSURE |
| |
| 3) 3RDREQUEST,2004 FBC 1609.1.3 PLEASE PROVIDE |
| INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST |
| THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING. |
| GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE SIZE |
| OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE |
| INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| REQUIRES WITHOUT LOAD REDUCTION. |
| |
| THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL |
| COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE |
| DESIGNER. FL.S .S 481.229 (ARCHITECT) OR FL.S.S 471.003 |
| (ENGINEER). THIS AREA IS IN A FLOOD ZONE AH; THEREFORE |
| THE ELEVATION OF THE CONCRETE SHALL BE A MINIMUM OF |
| 17'6", WHICH SHALL BE STATED OF THE ENGINEERED PLANS. |
| ALL DIMENSIONS FOR THE CONCRETE SLAB SHALL BE INDICATED |
| ON THE DRAWINGS INCLUDING THE THICKNESS. INDICATE THE |
| CLEARANCE AROUND THE GENERATOR FOR MAINTENANCE AND |
| REPAIR WORK. |
| |
| **NOTE** IN ORDER TO PROVIDE CONFORMITY TO OUR RECORD |
| RETENTION PROGRAM 'NO WHITE-OUT OR HANDWRITING IN PEN |
| OR PENCIL' ON THE DRAWINGS OR REPORTS WILL BE |
| ACCEPTABLE. CLEARLY STATE IF THE GENERATOR IS USED FOR |
| LIFE SAFETY ISSUES. |
| |
| BUILDING PLAN REVIEW |
| MYRON JACOBS |
| TEL: (561)805-6726 |
| FAX: (561)805-6676 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |