2007-12-05 16:15:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED 2ND TIME: |
| |
| **PLEASE SEE THAT MOST COMMENTS FROM THE PREVIOUS GAS |
| PLAN REVIEW REMAIN. |
| |
| 1. NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND |
| DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY. |
| PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND |
| NOT IN SETS. PER *106.3.1, APPROVAL OF CONSTRUCTION |
| DOCUMENTS AND *106.1.2 ADDITIONAL DATA. |
| |
| 2. PROVIDE TWO (2) COPIES OF A SITE PLAN OR SURVEY |
| THAT CLEARLY INDICATES THE PROPOSED LOCATION OF THE |
| GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES |
| AND ADJACENT DWELLING STRUCTURES. |
| **NOTE: COMMENT NOT ADDRESSED. |
| |
| 3. OK, COMMENT ADDRESSED. |
| |
| 4. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| **NOTE: COMMENT NOT ADDRESSED. |
| |
| 5. WHAT TYPE OF GAS GAS IS BEING USED. (LP OR |
| NATURAL) |
| **NOTE: COMMENT IS ADDRESSED IN THE SUBMITTED |
| MANUFACTURE SPECIFICATIONS BY INDICATING GENERATOR IS A |
| DUEL FUEL GENERATOR. HOWEVER THERE ARE NO ISOMETRIC GAS |
| RISER DIAGRAMS SUBMITTED TO INDICATE GENERATOR IS DUEL |
| FUEL. |
| |
| 6. OK, COMMENT ADDRESSED. |
| |
| 7. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| **NOTE: COMMENT NOT ADDRESSED. THERE WERE NO GAS |
| ISOMETRIC RISER DIAGRAMS IN THE RESUBMITTAL. |
| |
| 8. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| **NOTE: COMMENT NOT ADDRESSED. |
| |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| IF GAS DELIVERY PRESSURE IS GREATER THAN 2 PSI PLEASE |
| SUBMIT TWO (2) COPIES OF THE MP REGULATORS BEING USED |
| WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A |
| LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| LABORATORY. |
| **NOTE: COMMENT NOT ADDRESSED. |
| |
| 10. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED |
| MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING |
| GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP |
| TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW |
| OR EXISTING ON THE RESUBMITTAL. |
| |
| 11. 11. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 6.6.1. |
| NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED |
| MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING |
| GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP |
| TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW |
| OR EXISTING ON THE RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |