Plan Review Notes
Plan Review Notes For Permit 07090466
Permit Number 07090466
Review Stop G
Sequence Number 2
Notes
Date Text
2007-12-05 16:15:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PLEASE SEE THAT MOST COMMENTS FROM THE PREVIOUS GAS
 PLAN REVIEW REMAIN.
  
 1. NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND
 DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY.
 PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND
 NOT IN SETS. PER *106.3.1, APPROVAL OF CONSTRUCTION
 DOCUMENTS AND *106.1.2 ADDITIONAL DATA.
  
 2. PROVIDE TWO (2) COPIES OF A SITE PLAN OR SURVEY
 THAT CLEARLY INDICATES THE PROPOSED LOCATION OF THE
 GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES
 AND ADJACENT DWELLING STRUCTURES.
 **NOTE: COMMENT NOT ADDRESSED.
  
 3. OK, COMMENT ADDRESSED.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: COMMENT NOT ADDRESSED.
  
 5. WHAT TYPE OF GAS GAS IS BEING USED. (LP OR
 NATURAL)
 **NOTE: COMMENT IS ADDRESSED IN THE SUBMITTED
 MANUFACTURE SPECIFICATIONS BY INDICATING GENERATOR IS A
 DUEL FUEL GENERATOR. HOWEVER THERE ARE NO ISOMETRIC GAS
 RISER DIAGRAMS SUBMITTED TO INDICATE GENERATOR IS DUEL
 FUEL.
  
 6. OK, COMMENT ADDRESSED.
  
 7. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NOTE: COMMENT NOT ADDRESSED. THERE WERE NO GAS
 ISOMETRIC RISER DIAGRAMS IN THE RESUBMITTAL.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 **NOTE: COMMENT NOT ADDRESSED.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 IF GAS DELIVERY PRESSURE IS GREATER THAN 2 PSI PLEASE
 SUBMIT TWO (2) COPIES OF THE MP REGULATORS BEING USED
 WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 **NOTE: COMMENT NOT ADDRESSED.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED
 MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING
 GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP
 TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW
 OR EXISTING ON THE RESUBMITTAL.
  
 11. 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.6.1.
 NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED
 MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING
 GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP
 TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW
 OR EXISTING ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731