2007-12-19 14:18:35***DENIED***
 PLEASE NOTE THAT MOST COMMENTS HAVE NOT BEEN
 ADDRESSED.
  
 1) MINIMUM OF TWO (2) SETS OF MANUFACTURER
 SPECIFICATION SHEETS ARE REQUIRED. PLEASE INCLUDE ALL
 DOCUMENTS TO MAKE COMPLETE SUBMITTALS.
  
 2) OK
  
 3) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS. PLEASE ADD NOTE TO
 DRAWINGS.
  
 4) ALTHOUGH ORIGINAL GENERATOR WAS EXISTING, PROTECTION
 AROUND THE GENERATOR MAY BE REQUIRED IF THE POSSIBILITY
 OF EXPOSURE TO MECHANICAL DAMAGE EXISTS.
  
 5)WHAT BUILDING FIRE PROTECTION EQUIPMENT IS TIED TO
 AND POWERED BY THE GENERATOR DURING EMERGENCY
 OPERATIONS?
  
 NEW COMMENT:
  
 PLEASE CLEARLY ILLUSTRATE THE LOCATION OF THE GENERATOR
 AND ASSOCIATED CLEARANCES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756