2007-12-03 13:57:03 | |
| ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW |
| REMAIN. |
| |
| 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND |
| DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY. |
| PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND |
| NOT IN SETS. |
| FBC 106.3.1, 106.1.2 |
| |
| 2) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH |
| MOST STILL REMAIN. |
| NEED TO KNOW THE OCCUPANCY OF PROJECT. |
| NEED PLANS SHOWING LOCATION(S) FOR ALL EQUIPMENT, |
| SERVICE EQUIPMENT ETC. |
| NEED TO SHOW ALL RELEVANT CODES. |
| NEED TO HAVE THE DESIGNER OF RECORD. |
| ETC. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE COPIED FROM PREVIOUS |
| REVIEW. |
| |
| ** DENIED** |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED. |
| |
| 2) NOTE: PLEASE SUBMIT LOADS ON THIS EXISTING/NEW |
| GENERATOR TO BE INSTALLED. |
| PLEASE PROVIDE INFORMATION IF THIS UNIT FEEDS ANY |
| EMERGENCY LIFE SAFETY SYSTEMS OR LEGALLY REQUIRED |
| SYSTEMS.700, 701, |
| PLEASE SEE 700.12B3, 701.11B3 AS ANY LIFE SAFETY, OR |
| LEGALLY REQUIRED SYSTEMS FED BY THIS UNIT WILL REQUIRE |
| *ON-SITE* FUEL MEETING THE MINIMUM LOADS FOR THE |
| MINIMUM SPECIFIED TIMES DEPENDING ON INSTALLATION. WHAT |
| ARE THE INTENDED LOADS? 701.5, 700.5, 702.5 |
| |
| 3) NOTE: PLEASE SEE AS OCCUPATION FOR THE DESIGNATED |
| GENERATOR IS NOT KNOWN, PLEASE BE AWARE OF HOUSE BILL |
| 7121 FOR STAND-BY SYSTEMS AND REQUIRED ON-SITE FUEL. |
| |
| 4) NOTE: OK |
| |
| 5) NOTE: PLEASE SEE FS 481.229 AND 471.003, EVEN WHEN |
| THE SCOPE OF WORK IS NOT REQUIRED TO BE DONE BY AN |
| ARCHITECT OR ENGINEER, THE SCOPE OF WORK STILL REQUIRES |
| THE DESIGN TO CONTAIN THE PRINTED NAME AND SIGNATURE OF |
| THE PERSON TAKING RESPONSIBILITY OF SAID PLANS. |
| 106.3.5, 106.1.2 |
| |
| 6) NOTE: PLEASE SEE POSSIBLE BUILDING COMMENTS WITH |
| RESPECT TO ANY FLOOD ZONE WHICH WOULD REQUIRE THE |
| GENERATOR TO BE MOUNTED 6INCHES ABOVE BFE> (IF IN FLOOD |
| ZONE). |
| |
| 7) NOTE: PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS |
| SPECS/CUT SHEETS. |
| FBC 106.1 |
| |
| 8) NOTE: PLEASE PROVIDE SITE/OVERVIEW OF THE LOCATION |
| OF THIS UNIT AND ALL RELEVANT EQUIPMENT. |
| PLEASE SEE 225.31-225.39 FOR REQUIRED DISCONNECTING |
| MEANS FOR FEEDERS FROM THE GENERATOR. |
| AS NO SITE PLANS AND OTHER NEEDED INFORMATION WAS |
| SUBMITTED NO REVIEW OF THIS FOR CODE COMPLIANCE CAN BE |
| DONE. |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| PLANS. |
| |
| ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR |
| REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL |
| BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS |
| SUBMITTED. |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |