Plan Review Notes
Plan Review Notes For Permit 07090466
Permit Number 07090466
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-03 13:57:03 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW
 REMAIN.
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND
 DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY.
 PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND
 NOT IN SETS.
 FBC 106.3.1, 106.1.2
  
 2) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH
 MOST STILL REMAIN.
 NEED TO KNOW THE OCCUPANCY OF PROJECT.
 NEED PLANS SHOWING LOCATION(S) FOR ALL EQUIPMENT,
 SERVICE EQUIPMENT ETC.
 NEED TO SHOW ALL RELEVANT CODES.
 NEED TO HAVE THE DESIGNER OF RECORD.
 ETC.
  
 ** PLEASE SEE THE NOTES BELOW ARE COPIED FROM PREVIOUS
 REVIEW.
  
 ** DENIED**
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED.
  
 2) NOTE: PLEASE SUBMIT LOADS ON THIS EXISTING/NEW
 GENERATOR TO BE INSTALLED.
 PLEASE PROVIDE INFORMATION IF THIS UNIT FEEDS ANY
 EMERGENCY LIFE SAFETY SYSTEMS OR LEGALLY REQUIRED
 SYSTEMS.700, 701,
 PLEASE SEE 700.12B3, 701.11B3 AS ANY LIFE SAFETY, OR
 LEGALLY REQUIRED SYSTEMS FED BY THIS UNIT WILL REQUIRE
 *ON-SITE* FUEL MEETING THE MINIMUM LOADS FOR THE
 MINIMUM SPECIFIED TIMES DEPENDING ON INSTALLATION. WHAT
 ARE THE INTENDED LOADS? 701.5, 700.5, 702.5
  
 3) NOTE: PLEASE SEE AS OCCUPATION FOR THE DESIGNATED
 GENERATOR IS NOT KNOWN, PLEASE BE AWARE OF HOUSE BILL
 7121 FOR STAND-BY SYSTEMS AND REQUIRED ON-SITE FUEL.
  
 4) NOTE: OK
  
 5) NOTE: PLEASE SEE FS 481.229 AND 471.003, EVEN WHEN
 THE SCOPE OF WORK IS NOT REQUIRED TO BE DONE BY AN
 ARCHITECT OR ENGINEER, THE SCOPE OF WORK STILL REQUIRES
 THE DESIGN TO CONTAIN THE PRINTED NAME AND SIGNATURE OF
 THE PERSON TAKING RESPONSIBILITY OF SAID PLANS.
 106.3.5, 106.1.2
  
 6) NOTE: PLEASE SEE POSSIBLE BUILDING COMMENTS WITH
 RESPECT TO ANY FLOOD ZONE WHICH WOULD REQUIRE THE
 GENERATOR TO BE MOUNTED 6INCHES ABOVE BFE> (IF IN FLOOD
 ZONE).
  
 7) NOTE: PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS
 SPECS/CUT SHEETS.
 FBC 106.1
  
 8) NOTE: PLEASE PROVIDE SITE/OVERVIEW OF THE LOCATION
 OF THIS UNIT AND ALL RELEVANT EQUIPMENT.
 PLEASE SEE 225.31-225.39 FOR REQUIRED DISCONNECTING
 MEANS FOR FEEDERS FROM THE GENERATOR.
 AS NO SITE PLANS AND OTHER NEEDED INFORMATION WAS
 SUBMITTED NO REVIEW OF THIS FOR CODE COMPLIANCE CAN BE
 DONE.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved