Plan Review Notes For Permit 07090466 |
Permit Number |
07090466 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-26 13:32:41 | ***DENIED*** | | | | 1) MINIMUM OF TWO (2) SETS OF MANUFACTURER | | SPECIFICATION SHEETS ARE REQUIRED. | | | | 2) PLEASE CLARIFY IF THE FUEL SOURCE IS PROPANE, | | NATURAL GAS OR DUEL PHASE. IS THERE AN ON SITE FUEL | | SOURCE? | | | | 3) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY | | AND STANDBY POWER SYSTEMS. PLEASE ADD NOTE TO | | DRAWINGS. | | | | 4) ALTHOUGH ORIGINAL GENERATOR WAS EXISTING, PROTECTION | | AROUND THE GENERATOR MAY BE REQUIRED IF THE POSSIBILITY | | OF EXPOSURE TO MECHANICAL DAMAGE EXISTS. | | | | 5)WHAT BUILDING FIRE PROTECTION EQUIPMENT IS TIED TO | | AND POWERED BY THE GENERATOR DURING EMERGENCY | | OPERATIONS? | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|