Plan Review Notes
Plan Review Notes For Permit 07090466
Permit Number 07090466
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-26 13:32:41***DENIED***
  
 1) MINIMUM OF TWO (2) SETS OF MANUFACTURER
 SPECIFICATION SHEETS ARE REQUIRED.
  
 2) PLEASE CLARIFY IF THE FUEL SOURCE IS PROPANE,
 NATURAL GAS OR DUEL PHASE. IS THERE AN ON SITE FUEL
 SOURCE?
  
 3) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS. PLEASE ADD NOTE TO
 DRAWINGS.
  
 4) ALTHOUGH ORIGINAL GENERATOR WAS EXISTING, PROTECTION
 AROUND THE GENERATOR MAY BE REQUIRED IF THE POSSIBILITY
 OF EXPOSURE TO MECHANICAL DAMAGE EXISTS.
  
 5)WHAT BUILDING FIRE PROTECTION EQUIPMENT IS TIED TO
 AND POWERED BY THE GENERATOR DURING EMERGENCY
 OPERATIONS?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved