2007-10-14 14:43:40 | |
| |
| ** DENIED** |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED. |
| |
| 2) NOTE: PLEASE SUBMIT LOADS ON THIS EXISTING/NEW |
| GENERATOR TO BE INSTALLED. |
| PLEASE PROVIDE INFORMATION IF THIS UNIT FEEDS ANY |
| EMERGENCY LIFE SAFETY SYSTEMS OR LEGALLY REQUIRED |
| SYSTEMS.700, 701, |
| PLEASE SEE 700.12B3, 701.11B3 AS ANY LIFE SAFETY, OR |
| LEGALLY REQUIRED SYSTEMS FED BY THIS UNIT WILL REQUIRE |
| *ON-SITE* FUEL MEETING THE MINIMUM LOADS FOR THE |
| MINIMUM SPECIFIED TIMES DEPENDING ON INSTALLATION. WHAT |
| ARE THE INTENDED LOADS? 701.5, 700.5, 702.5 |
| |
| 3) NOTE: PLEASE SEE AS OCCUPATION FOR THE DESIGNATED |
| GENERATOR IS NOT KNOWN, PLEASE BE AWARE OF HOUSE BILL |
| 7121 FOR STAND-BY SYSTEMS AND REQUIRED ON-SITE FUEL. |
| |
| 4) NOTE: PLEASE SEE RISER IS MISSING *EQUIPMENT |
| GROUNDING CONDUCTOR* FROM GENERATOR TO ATS. |
| PLEASE SEE 250.110, 250.122 |
| |
| 5) NOTE: PLEASE SEE FS 481.229 AND 471.003, EVEN WHEN |
| THE SCOPE OF WORK IS NOT REQUIRED TO BE DONE BY AN |
| ARCHITECT OR ENGINEER, THE SCOPE OF WORK STILL REQUIRES |
| THE DESIGN TO CONTAIN THE PRINTED NAME AND SIGNATURE OF |
| THE PERSON TAKING RESPONSIBILITY OF SAID PLANS. |
| 106.3.5, 106.1.2 |
| |
| 6) NOTE: PLEASE SEE POSSIBLE BUILDING COMMENTS WITH |
| RESPECT TO ANY FLOOD ZONE WHICH WOULD REQUIRE THE |
| GENERATOR TO BE MOUNTED 6? ABOVE BFE> (IF IN FLOOD |
| ZONE). |
| |
| 7) NOTE: PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS |
| SPECS/CUT SHEETS. |
| FBC 106.1 |
| |
| 8) NOTE: PLEASE PROVIDE SITE/OVERVIEW OF THE LOCATION |
| OF THIS UNIT AND ALL RELEVANT EQUIPMENT. |
| PLEASE SEE 225.31-225.39 FOR REQUIRED DISCONNECTING |
| MEANS FOR FEEDERS FROM THE GENERATOR. |
| AS NO SITE PLANS AND OTHER NEEDED INFORMATION WAS |
| SUBMITTED NO REVIEW OF THIS FOR CODE COMPLIANCE CAN BE |
| DONE. |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| PLANS. |
| |
| ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR |
| REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL |
| BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS |
| SUBMITTED. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |