2007-10-20 09:47:03BUILDING PLAN REVIEW
 PERMIT: 07090466
 ADD: 1041 45TH STREET
 CONT: NEUTRON ELECTRIC
 TEL: (561)201-5005
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 2) MISSING INFORMATION ON PLAN IN REGARDS TO WIND: 2004
 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION RELATED
 TO WIND SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
  
 3) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE
 ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING.
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL
 COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE
 DESIGNER. FL S S 481.229 (ARCHITECT)OR FL S S 471.003
 (ENGINEER).
  
  
 4) PLEASE PROVIDE A SITE PLAN INDICA PROVIDE PLANS
 ENOUGH TO VERIFY LOCATION OF GENERATOR VERSES BUILDING
 OPENINGS WINDOWS, DOORS OR SOFFIT TYPE VENTS, ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS. HORIZONTAL
 TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR
 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET
 INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL NOT BE LOCATED
 CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER
 FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE MOUNTED
 DIRECTLY ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY
 FROM AN OIL TANK
 VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 12 INCHES (305 MM) ABOVE FINISHED
 GRADE.
  
 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.WHERE THE VENT TERMINATION IS LOCATED BELOW AN
 ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219
 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1
 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING. 5.A VENT CAP SHALL BE
 INSTALLED TO PREVENT RAIN FROM ENTERING THE VENT
 SYSTEM.
 6.THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3
 FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF
 STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM LOT LINES
 OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO THE
 CENTERLINE OF THE
 STREET OR PUBLIC WAY. TING THE LOCATION OF THE
 GENERATOR IN RELATIONSHIP TO OTHER STRUCTURES, PLEASE
 NOTE IF THERE ARE STRUCTURES WITHIN 10'-0" OF THE
 GENERATOR OPENINGS SUCH AS WINDOWS AND DOORS.
 ADDITIONAL INFORMATION REQUIRED. POSSIBLE MECHANICAL
 ISSUES.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  