2007-10-20 09:47:03 | BUILDING PLAN REVIEW |
| PERMIT: 07090466 |
| ADD: 1041 45TH STREET |
| CONT: NEUTRON ELECTRIC |
| TEL: (561)201-5005 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. |
| IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME |
| REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| 2004 FBC BUILDING WITH THE2007 REVISIONS. |
| |
| 2) MISSING INFORMATION ON PLAN IN REGARDS TO WIND: 2004 |
| FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION RELATED |
| TO WIND SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| |
| 3) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE |
| ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF |
| OVERTURNING, UPLIFT AND SLIDING. |
| GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE |
| SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE |
| INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| REQUIRES WITHOUT LOAD REDUCTION. |
| |
| THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL |
| COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE |
| DESIGNER. FL S S 481.229 (ARCHITECT)OR FL S S 471.003 |
| (ENGINEER). |
| |
| |
| 4) PLEASE PROVIDE A SITE PLAN INDICA PROVIDE PLANS |
| ENOUGH TO VERIFY LOCATION OF GENERATOR VERSES BUILDING |
| OPENINGS WINDOWS, DOORS OR SOFFIT TYPE VENTS, ETC. |
| |
| MECHANICAL CODE |
| 804.3.4 HORIZONTAL TERMINATIONS. HORIZONTAL |
| TERMINATIONS SHALL COMPLY WITH THE FOLLOWING |
| REQUIREMENTS: |
| 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE |
| TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT |
| LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE |
| WALKWAY. |
| 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) |
| ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 |
| MM). |
| 3.THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET |
| (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR |
| 1 FOOT |
| (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET |
| INTO THE BUILDING. |
| 4.THE VENT TERMINATION POINT SHALL NOT BE LOCATED |
| CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER |
| FORMED BY TWO |
| WALLS PERPENDICULAR TO EACH OTHER. |
| 5.THE VENT TERMINATION SHALL NOT BE MOUNTED |
| DIRECTLY ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY |
| FROM AN OIL TANK |
| VENT OR GAS METER. |
| 6.THE BOTTOM OF THE VENT TERMINATION SHALL BE |
| LOCATED AT LEAST 12 INCHES (305 MM) ABOVE FINISHED |
| GRADE. |
| |
| 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS |
| SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: |
| 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE |
| TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT |
| LESS THAN 7 |
| FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY. |
| 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) |
| ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 |
| MM). |
| 3.WHERE THE VENT TERMINATION IS LOCATED BELOW AN |
| ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE |
| LOCATED AT LEAST 3 FEET (914 MM) FROM |
| SUCH STRUCTURE. |
| 4.THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219 |
| MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1 |
| FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR |
| INLET FOR THE BUILDING. 5.A VENT CAP SHALL BE |
| INSTALLED TO PREVENT RAIN FROM ENTERING THE VENT |
| SYSTEM. |
| 6.THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3 |
| FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF |
| STRUCTURE. |
| |
| 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY |
| MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS |
| AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM |
| WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A |
| VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN |
| ATTIC OR CRAWL SPACE |
| |
| 401.5 OPENING LOCATION. |
| OUTDOOR AIR EXHAUST AND INTAKE OPENINGS SHALL BE |
| LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM LOT LINES |
| OR BUILDINGS ON |
| THE SAME LOT. WHERE OPENINGS FRONT ON A STREET OR |
| PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO THE |
| CENTERLINE OF THE |
| STREET OR PUBLIC WAY. TING THE LOCATION OF THE |
| GENERATOR IN RELATIONSHIP TO OTHER STRUCTURES, PLEASE |
| NOTE IF THERE ARE STRUCTURES WITHIN 10'-0" OF THE |
| GENERATOR OPENINGS SUCH AS WINDOWS AND DOORS. |
| ADDITIONAL INFORMATION REQUIRED. POSSIBLE MECHANICAL |
| ISSUES. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| |
| |
| |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |
| |