Plan Review Notes
Plan Review Notes For Permit 07090363
Permit Number 07090363
Review Stop P
Sequence Number 2
Notes
Date Text
2008-05-05 11:01:04PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS FOR THE
 PURPOSE OF CONTINUITY. NEW COMMENTS WILL BE SO NOTED
 FOLLOWING THE PREVIOUS REVIEW COMMENTS.
  
 1. PROVIDE TWO COPIES OF A SITE PLAN WITH THE
 FOLLOWING INFORMATION.
  
 A} POINT OF CONNECTION LOCATION OF THE PROPOSED 3/4"
 WATER SERVICE TO THE PROPOSED NEW FINGER DOCK BEING
 INDICATED ON THE ELECTRICAL PLAN. PER FBC PLUMBING
 SECTION *601.1 SCOPE.
 ** NOTE: AT A MINIMUM PLANS MUST BE CORRELATED. THE
 SUBMITTED SITE PLAN BY GENERAL PLUMBING INC.DOES NOT
 REFLECT THE SIGNED AND SEALED PLAN BY THE ENGINEER.THE
 SIGNED AND SEALED PLAN BY THE ENGINEER IS INDICATING
 3/4" SCH. 40 WATER LINE TO THE DOCK, HOWEVER THE PLAN
 BY THE PLUMBING CONTR. IS INDICATING A 1" PVC WATER
 LINE TO THE DOCK. PLEASE CORRELATE THE PLANS PER
 (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B} **OK** COMMENT ADDRESSED.
  
 C} **OK** COMMENT ADDRESSED.
  
 D} CLEARLY INDICATE IF THE DOCK IS GOING TO HAVE HOSE
 CONNECTIONS (SILLCOCK, HOSE BIBB, WALL HYDRANT OR OTHER
 TYPE OF HOSE CONNECTION) AND THE LOCATION OF THE HOSE
 CONNECTION AND THAT THE HOSE CONNECTIONS WILL BE
 PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM BREAKER. PER
 FBC PLUMBING SECTION *601.1 SCOPE AND SECTION
 608.15.4.2 HOSE CONNECTIONS.
 **NOTE: THE SUBMITTED PLANS BY GENERAL PLUMBING INC.
 DO NOT CLEARLY INDICATE THAT THE HOSE BIBBS ON THE DOCK
 WILL BE PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM
 BREAKER. PER FBC PLUMBING SECTION 601.1 SCOPE AND
 SECTION 608.15.4.2 HOSE CONNECTIONS.
  
 THE FOLLOWING ARE NEW COMMENTS.
  
 2. THE BACKFLOW ASSEMBLY MUST BE INSTALLED ON PRIVATE
 PROPERTY AS CLOSE TO THE SOURCE OF SUPPLY AS POSSIBLE.
 THE DOCK IS NOT CONSIDERED PRIVATE PROPERTY. PER CITY
 W.P.B. BACKFLOW DEPARMENT.
  
 3. PLANS SUBMITTED BY GENERAL PLUMBING INC. ARE
 INDICATING A 3/4" BACKFLOW PREVENTER BEING SUPPLIED BY
 A 1" LINE. PER FBC PLUMBING TABLE 603.1 (D.) ALL
 BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE AS
 THE LINE THEY ARE INSTALLED. IF IT IS THE INTENT TO
 HAVE A 1" SUPPLY LINE TO THE BACKFLOW PREVENTER THEN
 THE BACKFLOW PREVENTER MUST BE 1", ALSO THE SIGNED AND
 SEALED PLANS FROM THE ENGINEER MUST BE CHANGED TO
 REFLECT A 1" SUPPLY FROM METER TO BACKFLOW PREVENTER.
  
 4. THE SUBMITTAL FOR THE REDUCED PRESSURE PRINCIPLE
 BACKFLOW PREVENTER DOES NOT CLEARLY INDICATE THAT IT
 COMPLIES WITH ONE OF THE FOLLOWING APPLICABLE
 STANDARDS, ASSE 1013, AWWA C511, CAN/CSA B64.4. PER FBC
 PLUMBING TABLE 608.1 APPLICATION OF BACKFLOW
 PREVENTERS.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: THE PLUMBING CONTRACTOR GENERAL PLUMBING INC.
 MUST SIGN THEIR DRAWINGS AND SUBMITTALS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]