2008-02-25 15:27:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PROVIDE TWO COPIES OF A SITE PLAN WITH THE
 FOLLOWING INFORMATION.
  
 A} POINT OF CONNECTION LOCATION OF THE PROPOSED 3/4"
 WATER SERVICE TO THE PROPOSED NEW FINGER DOCK BEING
 INDICATED ON THE ELECTRICAL PLAN. PER FBC PLUMBING
 SECTION *601.1 SCOPE.
  
 B} LOCATION OF THE REQUIRED RPZV BACKFLOW PREVENTER
 (NOTE: THE RPZV BACKFLOW PREVENTER MUST BE INSTALLED ON
 PRIVATE PROPERTY AS CLOSE TO THE SOURCE OF SUPPLY (NEW
 FINGER DOCK) AS POSSIBLE). PER FBC PLUMBING SECTION
 *608.1 GENERAL.
  
 C} CLEARLY INDICATE THE PIPING MATERIAIL OF THE
 PROPOSED WATER SERVICE TO THE NEW FINGER DOCK AS WELL
 AS TO THE INLET AND OUTLET OF THE REQUIRED RPZV
 BACKFLOW PREVENTER. PER FBC PLUMBING SECTION *601.1
 SCOPE.
  
 D} CLEARLY INDICATE IF THE DOCK IS GOING TO HAVE HOSE
 CONNECTIONS (SILLCOCK, HOSE BIBB, WALL HYDRANT OR OTHER
 TYPE OF HOSE CONNECTION) AND THE LOCATION OF THE HOSE
 CONNECTION AND THAT THE HOSE CONNECTIONS WILL BE
 PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM BREAKER. PER
 FBC PLUMBING SECTION *601.1 SCOPE AND SECTION
 608.15.4.2 HOSE CONNECTIONS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER