2008-02-25 15:27:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. PROVIDE TWO COPIES OF A SITE PLAN WITH THE |
| FOLLOWING INFORMATION. |
| |
| A} POINT OF CONNECTION LOCATION OF THE PROPOSED 3/4" |
| WATER SERVICE TO THE PROPOSED NEW FINGER DOCK BEING |
| INDICATED ON THE ELECTRICAL PLAN. PER FBC PLUMBING |
| SECTION *601.1 SCOPE. |
| |
| B} LOCATION OF THE REQUIRED RPZV BACKFLOW PREVENTER |
| (NOTE: THE RPZV BACKFLOW PREVENTER MUST BE INSTALLED ON |
| PRIVATE PROPERTY AS CLOSE TO THE SOURCE OF SUPPLY (NEW |
| FINGER DOCK) AS POSSIBLE). PER FBC PLUMBING SECTION |
| *608.1 GENERAL. |
| |
| C} CLEARLY INDICATE THE PIPING MATERIAIL OF THE |
| PROPOSED WATER SERVICE TO THE NEW FINGER DOCK AS WELL |
| AS TO THE INLET AND OUTLET OF THE REQUIRED RPZV |
| BACKFLOW PREVENTER. PER FBC PLUMBING SECTION *601.1 |
| SCOPE. |
| |
| D} CLEARLY INDICATE IF THE DOCK IS GOING TO HAVE HOSE |
| CONNECTIONS (SILLCOCK, HOSE BIBB, WALL HYDRANT OR OTHER |
| TYPE OF HOSE CONNECTION) AND THE LOCATION OF THE HOSE |
| CONNECTION AND THAT THE HOSE CONNECTIONS WILL BE |
| PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM BREAKER. PER |
| FBC PLUMBING SECTION *601.1 SCOPE AND SECTION |
| 608.15.4.2 HOSE CONNECTIONS. |
| |
| END OF COMMENTS: |
| |