2008-01-15 16:40:06 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.THE WORK SPECIFIED IN THE ENGINEER'S LETTER IS NOT |
| WITHIN THE SCOPE OF THE ROOFING CONTRACTOR'S LICENSE |
| (STRUCTURAL REINFORCEMENT OF THE EXISTING ROOF RATERS). |
| ATTEMPTS TO RESOLVE THIS ISSUE WITH THE CONTRACTOR OVER |
| THE TELEPHONE WERE UNSUCCESSFUL AS THE CONTRACTOR |
| WANTED TO YELL ABOUT LAST NIGHT'S COMMISSION MEETING |
| RATHER THAN DISCUSS HOW I CAN ISSUE THIS REVISION AND |
| WHAT OPTIONS ARE AVAILABLE. |
| |
| 2.THE ENGINEER'S LETTER MAKES REFERENCE TO A |
| DIFFERENT PERMIT NUMBER AND ISLAND CONSTRUCTION.IF |
| AGREEABLE TO ISLAND CONSTRUCTION, THE STRUCTURAL WORK |
| CAN BE INCLUDED IN THEIR PERMIT WHEN ISSUED. |
| ALTERNATIVELY, A CONTRACTOR LICENSED TO DO THE WORK CAN |
| APPLY FOR A SUB PERMIT UNDER THIS ROOFING PERMIT. |
| |
| 3.AS THE REVISION CREATES AN ADDITIONAL DEAD LOAD ON |
| THE STRUCTURE WHICH THE EXISTING STRUCTURE CANNOT |
| ACCOMODATE (PER MESA ENGINEERING), THIS REVISION CANNOT |
| BE ISSUED UNTIL THE STRUCTURAL ISSUE/PERMIT IS |
| ADDRESSED. |
| |
| 4.FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED, |
| FAC9B72.THE LETTER MAKES REFERENCE TO MONIER CONCRETE |
| TILE; PLEASE PROVIDE APPROPRIATE PRODUCT APPROVALS. |
| |
| 5.ON THE TILE PRODUCT APPROVAL, PLEASE MARK THE |
| METHOD OF ATTACHMENT PROPOSED. |
| |
| |