Plan Review Notes
Plan Review Notes For Permit 07090304
Permit Number 07090304
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-13 13:57:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SHOW 872 SQUARE FEET OF
 A/C SPACE, BUILDING PLANS ON FILE SHOW 1,197 SQUARE
 FEET OF A/C SPACE. THE TWO MUST COINCIDE, PLEASE
 RE-CALCULATE COOLING LOAD CAL'S. WITH THE CORRECT
 SQUARE FEET OF COOLING SPACE.
  
 2) AFTER RE-DOING COOLING LOAD CAL'S. CHECK THE A/C
 EQUIPMENT LISTING ON THE PLANS FOR PROPER UNIT SIZE
 (CORRECT LISTING IF NEEDED).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]