Plan Review Notes
Plan Review Notes For Permit 07090221
Permit Number 07090221
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-26 11:17:35DENIED
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS, SECTIONS 424.2 OR
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 2006 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE PERMIT APPLICATION INDICATES A PLUMBING PERMIT
 BUT THE PLANS ARE INDICATING "ALL EXISTING PLUMBING TO
 REMAIN UNCHANGED & FUNCTIONAL. NO ADDITIONAL PLUMBING
 MODIFICATIONS WILL BE PERFORMED. ALL POOL/SPA
 CIRCULATION EQUIPMENT TO REMAIN UNCHANGED &
 FUNCTIONAL." THIS IS CONFUSING. THEN IN THE SUBMITTAL
 PACKAGE THERE IS A SIGNED, PROPOSAL/WORK ORDER
 INDICATING A NEW PUMP AND FILTER $850.00, REPLUMB EQ.
 $500.00 AND SALT SYSTEM AND AUTOMATION (4200 OPTION).
 PLEASE CORRELATE THE PLANS WITH THE SIGNED
 PROPOSAL/WORK ORDER ON THE RESUBMITTAL PER 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER