2007-09-13 07:45:32 | |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE BE SURE TO STATE THE RELEVANT CODES ON |
| PLANS |
| 2004 FBC W/2006 REVISIONS. |
| 2002 NFPA-72 |
| 2005 NFPA-70 |
| |
| 2) NOTE: PLEASE SEE FBC RESIDENTIAL CODE R313 AS ANY |
| NEW WORK IN UNIT IS REQUIRED TO HAVE THE SMOKE ALARMS |
| BROUGHT UP TO CODE MEETING NFPA-72 11.5.1.1.1. IF THESE |
| CURRENTLY ARE MEETING THE LATEST EDITION OF NFPA-72 |
| PLEASE INDICATE THESE ON PLANS. |
| |
| 3) NOTE: PLEASE SEE NEC 210.12 FOR NEW INSTALLED FOR |
| ARC FAULT PROTECTION. |
| |
| 4) NOTE: PLEASE SEE PLANS INDICATE NEW OVEN, COOK-TOP |
| AND MICROWAVE HOWEVER NO INFORMATION ON THE ELECTRICAL |
| IS SHOWN. WILL BE THIS BE NEW CIRCUITS, RECEPTACLES? IF |
| SO, PLEASE SUBMIT A PANEL SCHEDULE WITH THE MINIMUM |
| CONDUCTOR SIZES, OVER CURRENT PROTECTION AND EXISTING |
| LOAD WITH NEW LOAD ON PANEL. |
| IF THIS IS GOING TO BE FROM EXISTING CIRCUITS, PLEASE |
| INDICATE. |
| 408.4, 310.16, 240.4, |
| FBC 106.3.5.4, 106.3.5.1.2, 106.1.2 |
| |
| 5) NOTE: PLEASE KNOW EVEN WHEN SCOPE OF WORK FALLS |
| UNDER THE EXCEPTIONS OF 471 AND 481 OF THE FLORIDA |
| STATUTES, THE SCOPE OF WORK STILL REQUIRES THE PLANS TO |
| CONTAIN A PRINTED NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR PLANS. |
| PLEASE SEE FS 481.229 HOWEVER AS THE SCOPE OF WORK AS |
| APPLIED WILL REQUIRE AN ARCHITECT AT A MINIMUM. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |