Plan Review Notes
Plan Review Notes For Permit 07090147
Permit Number 07090147
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-13 07:45:32 
 ** DENIED **
  
 1) NOTE: PLEASE BE SURE TO STATE THE RELEVANT CODES ON
 PLANS
 2004 FBC W/2006 REVISIONS.
 2002 NFPA-72
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE FBC RESIDENTIAL CODE R313 AS ANY
 NEW WORK IN UNIT IS REQUIRED TO HAVE THE SMOKE ALARMS
 BROUGHT UP TO CODE MEETING NFPA-72 11.5.1.1.1. IF THESE
 CURRENTLY ARE MEETING THE LATEST EDITION OF NFPA-72
 PLEASE INDICATE THESE ON PLANS.
  
 3) NOTE: PLEASE SEE NEC 210.12 FOR NEW INSTALLED FOR
 ARC FAULT PROTECTION.
  
 4) NOTE: PLEASE SEE PLANS INDICATE NEW OVEN, COOK-TOP
 AND MICROWAVE HOWEVER NO INFORMATION ON THE ELECTRICAL
 IS SHOWN. WILL BE THIS BE NEW CIRCUITS, RECEPTACLES? IF
 SO, PLEASE SUBMIT A PANEL SCHEDULE WITH THE MINIMUM
 CONDUCTOR SIZES, OVER CURRENT PROTECTION AND EXISTING
 LOAD WITH NEW LOAD ON PANEL.
 IF THIS IS GOING TO BE FROM EXISTING CIRCUITS, PLEASE
 INDICATE.
 408.4, 310.16, 240.4,
 FBC 106.3.5.4, 106.3.5.1.2, 106.1.2
  
 5) NOTE: PLEASE KNOW EVEN WHEN SCOPE OF WORK FALLS
 UNDER THE EXCEPTIONS OF 471 AND 481 OF THE FLORIDA
 STATUTES, THE SCOPE OF WORK STILL REQUIRES THE PLANS TO
 CONTAIN A PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS.
 PLEASE SEE FS 481.229 HOWEVER AS THE SCOPE OF WORK AS
 APPLIED WILL REQUIRE AN ARCHITECT AT A MINIMUM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]