Plan Review Notes
Plan Review Notes For Permit 07090125
Permit Number 07090125
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-04 11:40:38CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07090125 BUILDING
 PLAN EXAMINERII PROJECT GOVT.
 CENTER LOBBY
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 301 N. OLIVE AVENUE
  DATE OCTOBER 4, 2007
  
 BUILDINGPLANREVIEW
  
  
  F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
  THE ENGINEERING CALCULATIONS PROVIDED BY THE DESIGNER
 OF RECORD AND SUBMITTED BY THE GENERAL CONTRACTOR
 CONTAIN SOME PHOTO COPIES OF THE DESIGNER?S SIGNATURE.
 WE CANNOT ACCEPT PHOTO COPIES OF ORIGINAL
 CALCULATIONS.
  
 COMMENT-PLEASE SEE THE SHEETS HIGH-LIGHTED IN YELLOW
 AND REPLACE SAME WITH ORIGINAL SIGNATURE AND SEAL.
 THANK YOU FOR YOUR ATTENTION TO THIS MATTER
  
  
  F. S. 471.025ENGINEER SEAL
 THE BOARD SHALL PRESCRIBE, BY RULE, ONE OR MORE FORMS
 OF SEAL TO BE USED BY LICENSEES. EACH LICENSEE SHALL
 OBTAIN AT LEAST ONE SEAL IN THE FORM APPROVED BY RULE
 OF THE BOARD AND MAY, IN ADDITION, REGISTER HIS OR HER
 SEAL ELECTRONICALLY IN ACCORDANCE WITH SS.
 668.001-668.006. ALL FINAL DRAWINGS, SPECIFICATIONS,
 PLANS, REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD AND ALL
 FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER'S
 REPRESENTATIVE SHALL BE SIGNED BY THE LICENSEE, DATED,
 AND SEALED WITH SAID SEAL. SUCH SIGNATURE, DATE, AND
 SEAL SHALL BE EVIDENCE OF THE AUTHENTICITY OF THAT TO
 WHICH THEY ARE AFFIXED. DRAWINGS, SPECIFICATIONS,
 PLANS, REPORTS, FINAL DOCUMENTS, OR DOCUMENTS PREPARED
 OR ISSUED BY A LICENSEE MAY BE TRANSMITTED
 ELECTRONICALLY AND MAY BE SIGNED BY THE LICENSEE,
 DATED, AND SEALED ELECTRONICALLY WITH SAID SEAL IN
 ACCORDANCE WITH SS. 668.001-668.006.
 COMMENT-FOR YOUR REFERENCE
  
  
 1 DESIGN INFORMATION REQUIRED
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FBC2004 ACCESSIBILITYCHAPTER 11
 FBC2004 EXISTING BUILDING
 LEVEL OF ALTERATION LEVEL 1
 WIND SPEED AND EXPOSURE
 WIND IMPORTANCE FACTOR
 COMMENT ?PLEASE NOTE ON COVER SHEET
  
  
 1.A 303.1 SCOPE.LEVEL 1 ALTERATION
 LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT
 OR THE COVERING OF EXISTING MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE.
 LEVEL 1 ALTERATIONS SHALL NOT INCLUDE ANY REMOVAL,
 REPLACEMENT OR COVERING OF EXISTING MATERIALS,
 ELEMENTS, EQUIPMENT OR FIXTURES UNDERTAKEN FOR PURPOSE
 OF REPAIR AS DEFINED IN CHAPTER 2 AND DESCRIBED IN
 SECTION 302 .
 COMMENT-FOR YOUR REFERENCE
  
  
 1.B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
 COMMENT-PLEASE NOTE WIND DESIGN SPEED, IMPORTANCE
 FACTOR, EXPOSURE
  
  
 1C FBC 1604.5 TABLE FOR WIND IMPORTANCE FACTOR
 THE VALUE FOR WIND LOAD IMPORTANCE FACTOR SHALL BE
 DETERMINED IN ACCORDANCE WITH TABLE 1604.5 .
 COMMENT-FOR YOUR REFERENCE
  
  
 2 SHEET E-1/A-1
 DETAIL ASTEEL TUBE COLUMN ?NEW WORK LEGEND?STATES
 BASE PLATE ANCHOR IS MIN. 5/8?
 BASE PLATE DETAIL STATES ANCHOR IS 3/4?.
 COMMENT- WHICH SIZE WILL BE USED?
  
 3 SHEET E-1/A-1
 DETAIL CPROVIDE DETAILS / SECTION FOR METAL STUD
 FRAMING, TYPE OF FASTENER USED FOR FRAMING COMPONENTS,
 WOOD STRUCTURAL PANEL NOMENCLATURE,PANEL ID, FASTENER
 USED FOR THIS PRODUCT,
 COMMENT- PLEASE PROVIDE THE INFORMATION LISTED HEREIN
  
  
 3.A 2303.1.4 WOOD STRUCTURAL PANELS.
 WOOD STRUCTURAL PANELS, WHEN USED STRUCTURALLY
 (INCLUDING THOSE USED FOR SIDING, ROOF AND WALL
 SHEATHING, SUBFLOORING, DIAPHRAGMS AND BUILT-UP
 MEMBERS), SHALL CONFORM TO THE REQUIREMENTS FOR THEIR
 TYPE IN DOC PS 1 OR PS 2. EACH PANEL OR MEMBER SHALL BE
 IDENTIFIED FOR GRADE AND GLUE TYPE BY THE TRADEMARKS OF
 AN APPROVED TESTING AND GRADING AGENCY. WOOD STRUCTURAL
 PANEL COMPONENTS SHALL BE DESIGNED AND FABRICATED IN
 ACCORDANCE WITH THE APPLICABLE STANDARDS LISTED IN
 SECTION 2306.1 AND IDENTIFIED BY THE TRADEMARKS OF AN
 APPROVED TESTING AND INSPECTION AGENCY INDICATING
 CONFORMANCE WITH THE APPLICABLE STANDARD. IN ADDITION,
 WOOD STRUCTURAL PANELS WHEN PERMANENTLY EXPOSED IN
 OUTDOOR APPLICATIONS SHALL BE OF EXTERIOR TYPE, EXCEPT
 THAT WOOD STRUCTURAL PANEL ROOF SHEATHING EXPOSED TO
 THE OUTDOORS ON THE UNDERSIDE IS PERMITTED TO BE
 INTERIOR TYPE BONDED WITH EXTERIOR GLUE, EXPOSURE 1
  
  
  
  
  
 3.B 2304.6.1 WOOD STRUCTURAL PANEL SHEATHING. WHERE
 WOOD STRUCTURAL PANEL SHEATHING IS USED AS THE EXPOSED
 FINISH ON THE EXTERIOR OF OUTSIDE WALLS, IT SHALL HAVE
 AN EXTERIOR EXPOSURE DURABILITY CLASSIFICATION. WHERE
 WOOD STRUCTURAL PANEL SHEATHING IS USED ON THE EXTERIOR
 OF OUTSIDE WALLS BUT NOT AS THE EXPOSED FINISH, IT
 SHALL BE OF A TYPE MANUFACTURED WITH EXTERIOR GLUE
 (EXPOSURE 1 OR EXTERIOR). WHERE WOOD STRUCTURAL PANEL
 SHEATHING IS USED ELSEWHERE, IT SHALL BE OF A TYPE
 MANUFACTURED WITH INTERMEDIATE OR EXTERIOR GLUE.
 COMMENT-PANEL ID
  
 3.C TABLE 2308.9.3(3) WOOD STRUCTURAL PANEL WALL
 SHEATHING
 (NOT EXPOSED TO THE WEATHER, STRENGTH AXIS PARALLEL OR
 PERPENDICULAR TO STUDS
 COMMENT-SEE THIS TABLE FOR PLYWOOD SHEATHING
  
 3.D 2304.9.2 SHEATHING FASTENERS.
 SHEATHING NAILS OR OTHER APPROVED SHEATHING CONNECTORS
 SHALL BE DRIVEN SO THAT THEIR HEAD OR CROWN IS FLUSH
 WITH THE SURFACE OF THE SHEATHING. COMMENT-DESCRIBE
 TYPE OF FASTENER AND SPACING
  
 4 FBC 1609.1.3COMPONENTS & CLADDING
 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND SLIDING.
 STRUCTURAL MEMBERS AND SYSTEMS AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE SHALL BE ANCHORED
 TO RESIST WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING
 AND TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES
 TO THE FOUNDATION. WHERE A PORTION OF THE RESISTANCE TO
 THESE FORCES IS PROVIDED BY DEAD LOAD, THE DEAD LOAD,
 INCLUDING THE WEIGHT OF SOILS AND FOUNDATIONS, SHALL BE
 TAKEN AS THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT. WHERE THE ALTERNATE BASIC
 LOAD COMBINATIONS OF SECTION 1605.3.2 ARE USED, ONLY
 TWO-THIRDS OF THE MINIMUM DEAD LOAD LIKELY TO BE IN
 PLACE DURING A DESIGN WIND EVENT SHALL BE USED.
 COMMENT- FRAMING MEMBERS
  
 5 2304.6 WALL SHEATHING.
 EXCEPT AS PROVIDED FOR IN SECTION 1405 FOR
 WEATHERBOARDING OR WHERE STUCCO CONSTRUCTION THAT
 COMPLIES WITH SECTION 2510 IS INSTALLED, ENCLOSED
 BUILDINGS SHALL BE SHEATHED WITH ONE OF THE MATERIALS
 OF THE NOMINAL THICKNESS SPECIFIED IN TABLE 2304.6 OR
 ANY OTHER APPROVED MATERIAL OF EQUIVALENT STRENGTH OR
 DURABILITY.
 COMMENT-PLEASE IDENTIFY
  
  
 6 2512.1 GENERAL.
 PLASTERING WITH CEMENT PLASTER SHALL NOT BE LESS THAN
 THREE COATS WHERE APPLIED OVER METAL LATH OR WIRE
 FABRIC LATH AND NOT LESS THAN TWO COATS WHERE APPLIED
 OVER MASONRY, CONCRETE OR GYPSUM BOARD BACKING AS
 SPECIFIED IN SECTION 2510.5 . IF THE PLASTER SURFACE IS
 TO BE COMPLETELY COVERED BY VENEER OR OTHER FACING
 MATERIAL, OR IS COMPLETELY CONCEALED BY ANOTHER WALL,
 PLASTER APPLICATION NEED BE ONLY TWO COATS, PROVIDED
 THE TOTAL THICKNESS IS AS SET FORTH IN ASTM C 926.
 COMMENT-PLEASE STATE TYPE OF LATH, FASTENING TO BE USED
 IN COMPLIANCE WITH THIS SECTION.
  
 7 FBC2507.2 STANDARDS.
 LATHING AND PLASTERING MATERIALS SHALL CONFORM TO THE
 STANDARDS LISTED IN TABLE 2507.2 AND CHAPTER 35 AND,
 WHERE REQUIRED FOR FIRE PROTECTION, SHALL ALSO CONFORM
 TO THE PROVISIONS OF CHAPTER 7 .
 COMMENT-FOR YOUR INFORMATION
  
 8 DETAIL ?LOBBY PLAN VIEW? NOTE 2
 THE STORE FRONT DOOR AND GLAZING SYSTEM IS NOTED ON THE
 PRODUCT APPROVALS AS IMPACT RESISTANT.
 WHY ARE THE NOTES SPECIFYING SHUTTERS?