Plan Review Notes
Plan Review Notes For Permit 07090118
Permit Number 07090118
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-17 09:55:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-2004R OR
 YOU MAY USE THE SHORT FORM 600C-2004R. SEE FBC
 13-600.3.A AND 13-600.3.C.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) COOLING LOAD CALCULATIONS WERE SUBMITTED BUT PLANS
 SHOW NO A/C WORK TO BE DONE, PLEASE REMOVE COOLING LOAD
 CAL'S OR SUBMIT A/C PLANS.
  