2007-09-20 07:50:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE RAS117 8.1, "THE MINIMUM FASTENER SEPARATION
 SHALL NOT BE LESS THAN 4 IN. O.C."THE ENGINEER
 SPECIFIES 3" FOR ZONE 3.PLEASE REVISE ENHANCED
 FASTENER LETTER.IF THE ENGINEER DISAGREES WITH THIS
 COMMENT, PLEASE HAVE HIM CONTACT ME.A SET HAS BEEN
 RETAINED.
  