Plan Review Notes
Plan Review Notes For Permit 07090070
Permit Number 07090070
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-17 12:51:41DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. APPLICATION INDICATESREPAIR OF BACK PORCH, BUT
 PLANS INDICATE ADDITION. PLEASE CORRELATE APPLICATION,
 WHICH REQUIRES DESCRIPTION OF PROJECT IN DETAIL,AND
 PLANS. SECTION 105.1.
  
 2. SHT A1 AREA CALCULATIONS INDICATES NEW LIVING AREA
 251SF TO BE NEW BEDROOMS, BUT THE FLOOR PLAN SHOWS NEW
 FAMILY ROOM AND NEW LAUNDRY ROOM. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1.
  
 3. SHT A1 SANITARY RISER DIAGRAM. SHOW ALL PIPE SIZES.
 THE MINIMUM TRAP SIZE FOR A WASH MACHINE IS 2" PER
 TABLE 709.1, BUT RISER SHOWS 1-1/2" WASTE ARM TO THE
 TRAP. MINIMUM 2" WASTE ARM TO TRAP REQUIRED.--THE
 STACK SHALL BE A MINIMUM 3" UP TO THE SANITARY TEE PER
 SECTION 406.3. PLEASE INDICATED STACK SIZE.--THE
 WASH MACHINE REQUIRES A STANDPIPE MINIMUM 18" UPSTREAM
 OF THE TRAP. PLEASE SHOW ON RISER. SECTIONS 802.4 &
 1002.1.--A CLEANOUT IS REQUIRED ON THE STACK. THE
 CLEANOUT, IF TO THE OUTSIDE, CAN BE LOW AT THE BASE OF
 THE STACK. IF TO THE INSIDE SHALL BE SHOWN MINIMUM 4'
 ABOVE THE FLOOR FOR ACCESS. SECTIONS 708.3.4 & 708.9.
 INDICATE CLEANOUT ON RISER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  