2007-09-17 12:51:41 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. APPLICATION INDICATESREPAIR OF BACK PORCH, BUT |
| PLANS INDICATE ADDITION. PLEASE CORRELATE APPLICATION, |
| WHICH REQUIRES DESCRIPTION OF PROJECT IN DETAIL,AND |
| PLANS. SECTION 105.1. |
| |
| 2. SHT A1 AREA CALCULATIONS INDICATES NEW LIVING AREA |
| 251SF TO BE NEW BEDROOMS, BUT THE FLOOR PLAN SHOWS NEW |
| FAMILY ROOM AND NEW LAUNDRY ROOM. PLEASE CORRELATE |
| INFORMATION. SECTION 106.1.1. |
| |
| 3. SHT A1 SANITARY RISER DIAGRAM. SHOW ALL PIPE SIZES. |
| THE MINIMUM TRAP SIZE FOR A WASH MACHINE IS 2" PER |
| TABLE 709.1, BUT RISER SHOWS 1-1/2" WASTE ARM TO THE |
| TRAP. MINIMUM 2" WASTE ARM TO TRAP REQUIRED.--THE |
| STACK SHALL BE A MINIMUM 3" UP TO THE SANITARY TEE PER |
| SECTION 406.3. PLEASE INDICATED STACK SIZE.--THE |
| WASH MACHINE REQUIRES A STANDPIPE MINIMUM 18" UPSTREAM |
| OF THE TRAP. PLEASE SHOW ON RISER. SECTIONS 802.4 & |
| 1002.1.--A CLEANOUT IS REQUIRED ON THE STACK. THE |
| CLEANOUT, IF TO THE OUTSIDE, CAN BE LOW AT THE BASE OF |
| THE STACK. IF TO THE INSIDE SHALL BE SHOWN MINIMUM 4' |
| ABOVE THE FLOOR FOR ACCESS. SECTIONS 708.3.4 & 708.9. |
| INDICATE CLEANOUT ON RISER. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |