Plan Review Notes
Plan Review Notes For Permit 07090070
Permit Number 07090070
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-17 09:24:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PERMIT APPLICATION STATES REPAIR BACK PORCH, BUT THE
 PLANS SHOW AN ENCLOSED ADDITION (NEW FAMILY ROOM AND
 LAUNDRY ROOM) PLEASE CORRECT DESCRIPTION OF WORK ON
 PERMIT APPLICATION.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE FBC
 13-101.2.2.
  
 3) SHOW ON MECHANICAL PLANS THE SIZE OF THE RETURN AIR
 TRANSFER GRILLS TO THE TWO BEDROOMS, SEE RES. M1602.4.
  
 4) BUILDING PLANS SHOW EXISTING LIVING AREA AS 919 S/F,
 COOLING LOAD CALCULATIONS SHOW THE SQUARE FEET AS 741.
 PLEASE CORRECT COOLING LOAD CALCULATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]