Plan Review Notes For Permit 07090070 |
Permit Number |
07090070 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-14 15:18:56 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|