2008-03-27 09:49:47 | 1. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR |
| LOCATIONS. |
| |
| 2. THIS OFFICE PICKED UP ON THE EMERGENCY LIGHT |
| FIXTURES IDENTIFIED AS A, A1, H, AND Q, HOWEVER IT |
| APPEARS THAT ALL AREAS ARE NOT DIPLAYED. EMERGENCY |
| LIGHTING EQUIPMENT SHALL BE DISPLAYED FOR ALL AREAS OF |
| THE BUILDING. PLEASE REVIEW ALL LARGE ROOMS TO |
| DETERMINE IF EMERGENCY LIGHTING EQUIPMENT EXISTS FOR |
| THESE AREAS. PLEASE PROVIDE DRAWINGS. |
| |
| 3. THE FABRIC TRACK CEILING DISPLAYED ON PAGE A-6.0 |
| SHALL NOT INTERFERE WITH THE SPRAY PATTERN OF ANY |
| AUTOMATIC FIRE SPRINKLER HEADS. THE FIRE SPRINKLER |
| HEADS IN THIS AREA SHALL BE PROPERLY INSTALLED WITH |
| CONSIDERATION FOR THE FABRIC TRACK CEILING. |
| |
| 4. HOW IS THE COOK TOP GOING TO BE PROTECTED THAT IS |
| DISPLAYED ON PAGE A-7.2. THERE APPEARS TO BE NO HOOD, |
| DUCT OR FIRE SUPPRESSION SYSTEM ABOVE IT, ONLY A |
| MICROWAVE OVEN. |
| |
| 5. ANOTHER EXIT SIGN APPEARS TO BE NEEDED IN CORRIDOR |
| 300 TO DIRECT PERSONS TO WAITNG ROOM AREA EXIT 308 |
| NOTED ON PAGE E-3.0. |
| |
| 6. KEYPADS NOTED AT DOORS ON ELECTRICAL SHEETS |
| ILLUSTRATING FIRE ALARM EQUIPMENT. HOW DO THESE KEYPADS |
| WORK. HOW DOES SOMEONE EXIT IF THEY DO NOT KNOW THE |
| NUMBERS TO PUNCH. EVERY EMERGENCY DOES NOT ACTIVATE THE |
| FIRE ALARM SYSTEM. SOME EMERGENCIES COULD OCCUR THAT |
| DOES NOT IMMEDIATELY ACTIVATE THE FIRE SPRINKLER OR |
| FIRE ALARM SYSTEM. PLEASE EXPLAIN KEYPAD AND HOW DOES |
| IT WORK. |
| |
| 7. PLEASE PROVIDE DOCUMENTATION ON THERMAL BLANKET THAT |
| PROVIDES A TWO HOUR FIRE RATING ON PAGE M-2.3. |
| |
| 8. PLEASE INDICATE EXIT ROUTES AND EXIT LOCATIONS FROM |
| PARKING AREA. |
| |
| 9. ANY FIRE EXTINGUISHERS PLANNED FOR ACCESS TO PARKING |
| AREA. |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| 804-4709 PHONE |
| 804-4776 FAX |